York Gas Furnace: TM9T/TM9Y
Re: No Heat - Flashing Code 8
Code 8 = Flame was established but later lost - 5 times.
► This is a Soft-Lockout which will automatically reset after 1 hour.
Qty |
Possible Causes: |
4 |
Dirty Flame Sensor |
1 |
Water in Inducer |
|
Clogged Burners |
|
No or Low Gas Pressure |
|
Bad Gas Valve |
|
Combustion Air Problem |
|
Water in the Gas Line |
CHECKOUT:
1. Check Ignition Sequence
- If the furnace is running, turn the thermostat off and allow the furnace to cool and the blower to stop operating.
- Initiate a call for heat from the thermostat and monitor the ignition sequence.
- 1. The inducer motor should start with no difficulty.
- 2. The pressure switch should close within a couple seconds of the inducer starting.
- 3. The glow plug should energize within 30 seconds of the pressure switch closing.
- 4. The gas valve should open within 20 seconds of the glow plug energizing.
2. Check Ignition
- Visually inspect the burners during ignition.
- The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
3. Check Gas Pressure / Valve
- Inlet Gas Pressure
- Check the inlet gas pressure with the furnace off.
- Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
- Low Pressure = Bad Meter or Regulator
- Monitor the inlet gas pressure as the furnace attempts to ignite.
- Pressure Drops Below Minimum = Bad Meter/Regulator or Restricted Gas Line
- Manifold Gas Pressure
- The TM9Y uses a 2-stage gas valve. Make sure set the gas pressure at "High Fire".
- Check the manifold pressure when the furnace attempts to ignite.
- Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
- No Gas Pressure = Bad Gas Valve
- Low Gas Pressure ⇒ Increase Manifold Gas Pressure
- Normal Gas Pressure + No or Delayed Ignition = Clogged Burners
- Continue to monitor the manifold pressure throughout the burning process.
- Fluctuating manifold pressure may indicate Water in the Gas Line
4. Check Flame Sensor
- DC Voltage Method
- Set the multi-meter to 20 VDC.
- Find the two, round test ports of the right-side of the furnace control board marked, "FLAME CURRENT".
- Check for DC volts across the two test ports when the furnace fires.
- Direct Micro Amp Reading
- On the multi-meter switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Disconnect the wire from the flame sensor.
- Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
- Check the reading when the burners ignite.
- Normal Reading = 3.7 uA
- Low Flame Signal Warning = 1.5 MicroAmp
- Lockout Point = 0.1 MicroAmp
- Low Reading = Dirty Flame Sensor ⇒ Clean Flame Sensor & Re-check
- CAUTION! Move meter leads back to "COM" and "V" before proceeding!
5. Monitor Burners
- Allow the burners to operate.
- If possible, monitor the burners throughout the heating sequence with the burner door in-place.
- Watch for any fluttering of the burners.
- Normal Burning with Door Off + Fluttering with Door On = Recycling Exhaust or Combustion Air Problem