Knowledgebase

TM9Y - Flashing Code 1

Article ID: 385
Last updated: 24 Jan, 2019

York Gas Furnace: TM9Y

Re: Flashing Code 1

Code 1 = Flame sensed with no call for heat.

In a Code 1 situation, the furnace control board thinks that the gas valve is stuck on and the flame is still burning without a call for heat. Therefore, when a control board goes into a code 1, it will lock the inducer motor and blower motor on.


Qty Possible Causes:
Bad Control Board
1 Sticking Gas Valve
Shorted Flame Sensor
1 Mis-Wired Low Pressure (LP)


CHECKOUT:

1. Check Wiring

  • Ensure that the flame sensor wiring is correct.
    • On an LP gas furnace, a low gas pressure switch wires in series with the flame sensor.

2. Check Flame Sensor

  • Visually check the flame sensor for rust flakes or other items that may cause a false reading.
  • Check flame sensor Microamps when the burners shut-off.
    • No Microamp signal but controller locks-out = Bad Control Board

3. Check Gas Valve

  • Start the furnace with a call for heat
  • After the burners have been lit for at least 30 seconds, remove the "W" wire.
    • The burners should extinguish immediately.
      • Delayed shut-off = Sticking Gas Valve

This article was:   Helpful | Not helpful
Report an issue
Article ID: 385
Last updated: 24 Jan, 2019
Revision: 3
Access: Public
Views: 51
Comments: 0