York Gas Furnace: PT9
Re: Flashing Code 3
Code 3 = The 1LP pressure switch contact did not close during 1st stg heat operation, or the 2LP pressure switch contact did not close during 2nd stg heat operation
► The 1LP switch is typically rated for 0.75" w.c. and the 2LP switch is typically rated for 1.25." w.c.
► Both switches are 2-port (negative port from the inducer, positive to the enclosed burner box).
Qty |
Possible Causes: |
1 |
Bad Inducer Motor |
1 |
Item Stuck in Inducer |
|
Water in Vent |
|
Restricted Intake |
|
Clogged Drain/Trap |
|
Bad Pressure Switch |
CHECKOUT:
1. Check Inducer Motor Operation
- Start the furnace with a call for heat from the thermostat.
- Observe and listen to the inducer motor operation.
- Inducer Motor Starts → Step 2. Check Pressure Switch
- Inducer motor hums but does not start:
- Bad Inducer Motor or Capacitor
- Item in Inducer or Melted Blower Wheel ⇒ Remove inducer & check
- Sound of water "slurshing" = Water in Inducer ⇒ Remove the Inducer, pour out water, re-install inducer → Step 3. Check Condensate Drainage
- Listen for sounds of water in vent piping.
- If water is gurgling in vent, look for low spots that will hold water.
- Pipe must have constant slope back toward furnace.
2. Check Pressure Switches
- 1st Stage Heat
- Run the furnace on 1st stage only (un-hook W2 at the furnace if necessary).
- 1LP Switch Contacts
- Check for 24VAC between "C" on the terminal block and the Blue wire on 1LP.
- Check for 24VAC between "C" on the terminal block and the White wire on 1LP.
- Power On Both Sides = Switch Closed ⇒ Check 2nd Stage Heat
- Power on One Side Only = Switch Open ⇒ Check 1LP Pressure (below)
- Check 1LP Pressure
- Use a pressure meter to check the pressure at the 1LP switch.
- Must check positive & negative pressure together.
- Compare actual pressure to pressure rating on the switch.
- Pressure Near or Below the Switch Rating (0.75" w.c.) = Vent/Intake Issue ⇒ Check the negative pressure at the inducer and burner box individually.
- Inducer Negative Pressure Low = Vent or Drain Problem or Inducer Problem ⇒ Remove inducer & check for obstructions or damaged wheel.
- Burner Box Negative Pressure High = Intake Problem ⇒ Remove the burner box cover to see if pressure improves.
- Pressure Well Above Rating + Open Switch = Bad Switch or Water in Switch
- 2nd Stage Heat
- Run the furnace at full heating (place a jumper between W1 & W2 if necessary).
- 2LP Switch Contacts
- Check for 24VAC between "C" on the terminal block and the Org wire on 2LP.
- Check for 24VAC between "C" on the terminal block and the Blk wire on 2LP.
- Power On Both Sides = Switch Closed
- Power on One Side Only = Switch Open ⇒ Check 2LP Pressure (below)
- Check 2LP Pressure
- Use a pressure meter to check the pressure at the 2LP switch.
- Must check positive & negative pressure together.
- Compare actual pressure to pressure rating on the switch.
- Pressure Near or Below the Switch Rating (1.25" w.c.) = Vent/Intake Issue ⇒ Check the negative pressure at the inducer and burner box individually.
- Inducer Negative Pressure Low = Vent or Drain Problem or Inducer Problem ⇒ Remove inducer & check for obstructions or damaged wheel.
- Burner Box Negative Pressure High = Intake Problem ⇒ Remove the burner box cover to see if pressure improves.
- Pressure Well Above Rating + Open Switch = Bad Switch or Water in Switch
3. Check Condensate Drainage
- Remove the drain hoses from both Robber Drain Couplings on the inducer outlet.
- Water running out of coupling = Clogged Drainage
- On horizontal runs, make sure the drain outlets are pointed slightly down-hill.
- ► Look inside the drain fittings to make sure there is no obstruction.
- Remove the drain hoses from the inducer motor and collector box.
- Water running out of collector box or inducer = Clogged Drainage
- Make sure all drain hoses are clear and have a downward slope.
- ► Look inside the drain fittings to make sure there is no obstruction.
- Remove the hoses from the condensate trap.
- Water running out of hoses = Clogged Drainage
- Remove the condensate trap and make sure it is not clogged.
- ► In extreme cold conditions, be cautious of frozen drains.