TG9S/GY9S - Flashing Code 11

Article ID: 483
Last updated: 19 Nov, 2021

York Gas Furnace: TG9S/GY9S

Re: Flashing Code 11

This indicates that a primary or auxiliary limit switch has opened and has remained open for more than five minutes. This condition is usually associated with an air circulation failure. 

Code 11 is a Hard-Lockout which requires cycling 24VAC power to the furnace board to reset (or cycling 115V power).

Qty Possible Causes:
2 Bad Blower Motor
Bad Capacitor
1 Broken Blower Wheel
Bad Control Board
Bad Limit


CHECKOUT:

1. Check Blower Motor/Wheel

  • Turn off power to the furnace.
  • Open the blower access door and check the condition of the blower wheel.
  • Check to see if the motor and wheel turn freely.

2. Check Motor Operation

  • Turn on power to the furnace.
  • Energize a call for "Fan" by jumping "R" to "G".

3. Check Control Board/Motor

  • With a call for "Fan", check for 120VAC between "Neutral" and "HEAT", then "Neutral" and "COOL".
    • No Power = Bad Control Board It may be possible to hook a blower speed to the "EAC" terminal to get temporary fan operation.
    • Power Present + No Blower Operation = Bad Motor, Bad Capacitor or Bad Wiring Check motor temperature, capacitor and wiring.

4. Check Limits

  • Check for 24VAC between both sides of the primary limit and "C".
    • Power on Both Sides = Limit Closed
    • Power on One Side Only = Limit Open 
      • Limit Open + Cool Chamber = Bad Limit
  • Alternatively, check for 24VAC between the Red wire on Pin#1 and the Red/Grn wire on Pin#7 of the 12-pin plug.
    • No Power = Limit Closed
    • Power Present = Limit Open