Knowledgebase

TG9S/GY9S - Flashing Code 3

Article ID: 294
Last updated: 5 Apr, 2024

York 90% Gas Furnace: TG9S

Re: Flashing Code 3

Code 3 = Furnace Pressure Switch failed to close on a call for heat.

►The code description on the blower door says, "Vent or Termination Problem" which is a possible cause, but not the most likely.


This gas furnace has two pressure switches:

  • A low pressure switch that monitors for a clogged drain (typically -0.20" w.c.).
  • A higher pressure switch that monitors the negative pressure from the inducer (typically around -1.00" w.c.).

Either switch open after the inducer motor is commanded to start will generate a Code 3.


Qty Possible Causes:
11 Bad Inducer Motor
4 Water in inducer 
2 Clogged or Restricted Vent
2 Bad Vent Pressure Switch
4 Bad Drain Pressure Switch
2 Clogged / Frozen Drain
1 Pressure Hose Problem
Item Stuck in Inducer Motor
Bad Ignition Control


CHECKOUT:

1. Check Control Board

  • Start the furnace with a call for heat.
  • Ensure that power is present on "W" by checking for 24VAC between "W" and "C".
    • No Power = No Call for Heat
    • Power = The Inducer motor should start within 15 seconds.

2. Check Inducer

  • Observe and listen to the inducer motor.
    • Inducer motor runs normally → Step 3. Check Pressure Switches
    • Inducer motor hums but does not start = Bad Inducer Motor/Capacitor or Item in Inducer ⇒ Remove inducer & check
    • Sound of Water "Slurshing" = Water in Inducer ⇒ Remove Inducer, pour out water, re-install inducer → Step 4.  Check Condensate Drainage
      • The only logical way for water to get into the inducer is by condensation over-running the rain gutter on the inducer outlet.
  • Listen for sounds of water in the vent piping (near the furnace and at the vent termination).
    • If water is gurgling in the vent, look for sags or low spots in the vent piping that will hold water.
      • The vent piping must have a constant slope back toward the furnace.

3. Check Pressure Switches

  • Ensure the drain and pressure switch hoses are in the proper location for the furnace orientation. (See attached file)
  • Make sure there are no sags in the pressure switch hoses that could hold water.
  • Start the furnace with a call for heat.
  • Check Drain Switch (Low Pressure Switch)
    • Switch Contacts
    • With the wires attached to the switch, check for 24VAC between each terminal of the switch and Common.
      • 24VAC On Both Sides = Switch Closed → Check Vent Switch
      • 24VAC On One Side Only = Open Switch ⇒ Check Switch Pressure (below)
    • Switch Pressure
    • Remove the Low Pressure Switch hose from the Collector Box.
    • Inspect the pressure switch hose for a:
      • Loose hose
      • Dry-rotted, cracked hose
      • Clogged hose
    • Connect a pressure meter to the Collector Box pressure port.
    • Compare actual pressure to the pressure rating on the switch.
      • Pressure Near or Below Rating = Clogged Drain → Step 4. Check Condensate Drainage
        • Pressure Well Above the Rating + Open Switch = Bad Switch or Water in Switch
          • ** A York Service Letter changes a .40" drain switch to a .20" **
  • ​​​​Check Vent Switch (High Pressure Switch)
    • Switch Contacts
    • With the wires attached to the switch, check for 24VAC between each terminal of the switch and Common.
      • 24VAC On Both Sides = Switch Closed 
      • 24VAC On One Side Only = Open Switch ⇒ Use a pressure meter to check the Switch Pressure (below).
    • Switch Pressure
    • Remove the High Pressure Switch hose from the Inducer Motor.
    • Inspect the pressure switch hose for a:
      • Loose hose
      • Dry-rotted, cracked hose
      • Clogged hose
    • Connect a pressure meter to the Inducer Motor pressure port.
    • Compare actual pressure to the pressure rating on the switch.
      • Pressure Near or Below Rating = Clogged or Restricted Vent
      • Pressure Well Above the Rating + Open Switch = Bad Switch or Water in Switch
        • ​​​​Water in Switch is usually caused by a mis-run pressure switch hose - should loop up so water drains back to the inducer (not the pressure switch).

4. Check Condensate Drainage

  • Check the rain gutter on the inducer outlet.
    • Remove the drain hose and look into the coupling for any blockage.
    • Make sure the drain hose is clear.
      • On horizontal runs, make sure the drain outlets are pointed slightly down-hill.
  • Check the drain hose from the collector box.
    • Make sure all drain hoses are clear and have a downward slope.
  • IMPORTANT! Make sure there is an "Air-Gap" in the PVC drain immediately upon exiting the furnace.
    • Any trap after the furnace before the air gap will cause drainage issues.
    • A tee running up to the air conditioner coil will act as an air gap.
  • In extreme cold conditions be cautious of Frozen Drains.

This article was:   Helpful | Not helpful
Report an issue
Article ID: 294
Last updated: 5 Apr, 2024
Revision: 69
Access: Public
Views: 1568
Comments: 0
Attached files