Knowledgebase

TG9S/GY9S - Flashing Code 10

Article ID: 223
Last updated: 19 Nov, 2021

York Gas Furnace: TG9S/GY9S

Re: Flashing Code 10 / Fault Code 10

Code 10 = Flame sensed with no call for heat.

► The furnace control board thinks that the gas valve is stuck on and flame is still burning without a call for heat. Therefore, when a control board goes into a Code 10, it will lock the inducer motor and blower motor on.


Qty Possible Causes (From Most to Least Likely):
Bad Control Board
Sticking Gas Valve
Shorted Flame Sensor


CHECKOUT:

1. Check Gas Valve

  • Start the furnace with a call for heat
  • After the burners have been lit for at least 30 seconds, remove the "W" wire.
    • The burners should extinguish immediately.
      • Delayed shut-off = Sticking Gas Valve

2. Check Flame Sensor

  • Visually check the flame sensor for rust or other items that may cause a false reading.
  • Check flame sensor Microamps with the burners off.
    • No Microamp signal but controller locks-out = Bad Control Board

This article was:   Helpful | Not helpful
Report an issue
Article ID: 223
Last updated: 19 Nov, 2021
Revision: 6
Access: Public
Views: 755
Comments: 0