Knowledgebase

Heat Pump - Low Heat

Article ID: 234
Last updated: 6 Nov, 2020

York Heat Pumps: Heating

Re: Low Heat

The customers reports that the heat pump doesn't provide enough heat and that they only get warm air when the auxiliary heat kicks on.

Other symptoms include: Higher than normal electric bill; System runs continuous.


Qty Possible Causes:
1 Refrigerant Charge
1 Bad Expansion Valve
No Power to O/D Unit
Bad Capacitor
Control in Lockout
Bad Compressor
Defrost Problem
Thermostat Issue
Ductwork Problem
Bad Control Board


CHECKOUT:

1. Check Unit Status & Power

  • Unit Status
  • Inspect the outdoor unit and make sure the outdoor coil is not frozen-over = Defrost Problem
  • Unit Operating --> Step 2. Check Compressor Operation
  • Power
  • Disconnect power to O/D unit by pulling disconnect or turning off breaker.
    • Open the electrical compartment cover. 
    • Inspect for burnt wiring or burnt contactor contacts.
  • Re-apply power to the unit.
  • Check for 200 - 240VAC power on the contactor inlet.
    • No Power = Tripped Breaker or Bad Wiring
  • Check for 24VAC between "R" and "C" on the defrost control board.
    • No Power = Blown Low Voltage Fuse or Bad Transformer
  • Set the Thermostat to call for heat.
    • Check for 24VAC between "Y" and "C" on the defrost control board.
      • No Power = No Call from the Thermostat ⇒ Check Thermostat
      • Power ⇒ Compressor and Condenser Fan should start within 5 minutes.

2. Check Compressor Operation

  • Re-Apply Power to the unit (if turned off from the previous step).
    • Compressor and Condenser Fan start and run normally Step 3. Check Refrigerant Pressures
    • Compressor Does Not Try to Start = Control in Lockout, Bad Control Board or Bad Contactor
      • Check for 24VAC between each "Pressure Switch" terminal and "C" on the defrost board.
        • Power on One Side Only = Open Hi or Lo Pressure Switch
        • Power on Both Sides = Pressure Safeties OK Reset control by disconnecting "R" and "Y" from the board then re-check.
          • Short the "TEST" terminals on the defrost control to bypass the "Wait" timer.
          • Check for 24VAC across both contactor coil wires.
            • Power + Contactor Doesn't Pull-in = Bad Contactor
            • No Power ⇒ Suspect Bad Control Board
    • Compressor Hums but Doesn't Run = Bad Capacitor, Locked-up Compressor, or Burnt Compressor Wiring

3. Check Refrigerant Pressures

  • Hook-up refrigerant gauges to the pressure ports on the unit.
    • Blue --> "True Suction" Port (Not Suction Line)
    • Red --> High Pressure (either refrigerant line)
  • Monitor pressures as the system operates.
Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge
  • If a Liquid-Line Sight Glass is installed, observe for bubbles in the sight glass (after the system has been operating for at least 5 min.)
    • Bubbles = Low Refrigerant Charge
  • Low Pressure Issues
    • Low Suction Pressure + Clear Sight Glass + Expansion Valve Frosting = Bad Expansion Valve 
    • Low Suction Pressure + Low Discharge Pressure + Bubbles in Sight Glass + Expansion Valve Frosting = Low Refrigerant Charge
      • Try adding refrigerant through the Low Pressure gauge.
        • Suction and Discharge Pressures should gradually increase as refrigerant is added.
        • If the Discharge Pressure increases but the Suction stays low or drops = Bad Expansion Valve
  • High Pressure Issues
    • Place an insulated temperature probe on the liquid line between the evaporator coil & O/D expansion valve.
    • Allow the unit to run for at least 10 minutes.
    • Monitor pressures and temperature as the system operates.
      • If pressure exceeds Normal Range or kicks-off on Hi Pressure safety in the first 5 minutes = Refrigerant Overcharge or No Indoor Blower
    • Check Sub-Cooling
      • Record "Saturation Temperature" from the discharge pressure gauge.
      • Subtract the Actual liquid line temperature reading.
        • Saturation Temp - Liquid Line Temp = Sub-Cooling
        • Normal Sub-Cooling = 4 - 13 deg.
          • High Sub-Cooling + High Discharge Pressure + Normal or High Suction Pressure  = Overcharged
          • High Sub-Cooling + High Discharge Pressure + Low Suction Pressure = Bad Expansion Valve
          • Low Sub-Cooling + High Discharge Pressure = Low Indoor Heat Transfer Step 5. Check Air Temperature Rise

4. Check Compressor Discharge Temperature

  • Use a multi-meter to check the temperature of the compressor discharge line.
  • Normal Temperature = 120 - 150 deg.
    • Low Discharge Temp = Inefficient Operation

5. Check Air Temperature Rise

  • With the auxiliary heaters disconnected (remove "W1" and "W2" form the air handler terminal block):
    • Check the Return Air Temperature near the unit or in the filter compartment.
    • Check the Supply Air Temperature.
    • Normal Temperature Rise = 15-20 deg.
      • Abnormally Low Return Air Temperature ⇒ Check Return Ductwork for Cold Air Infiltration
      • Low Temperature Rise = Inefficient Operation
        • Be cautious of "Directional Heat Issue"
      • High Temperature Rise = Low Airflow
    • RE-HOOK "W1" AND "W2" WIRES ON THE AIR HANDLER!

This article was:   Helpful | Not helpful
Report an issue
Article ID: 234
Last updated: 6 Nov, 2020
Revision: 11
Access: Public
Views: 53
Comments: 0