Heat Pump - Low Heat

York Heat Pumps: Heating

Re: Low Heat

The customers reports that the heat pump doesn't provide enough heat and that they only get warm air when the auxiliary heat kicks on.

Other symptoms include: Higher than normal electric bill; System runs continuous.


Qty Possible Causes:
1 Refrigerant Charge
1 Bad Expansion Valve
No Power to O/D Unit
Bad Capacitor
Control in Lockout
Bad Compressor
Defrost Problem
Thermostat Issue
Ductwork Problem
Bad Control Board


CHECKOUT:

1. Check Unit Status & Power


2. Check Compressor Operation


3. Check Refrigerant Pressures

Normal Pressure Range
Refrigerant 0-30 Deg O/D 30-50 Deg O/D
R410A
  • 75-100 Suction
  • 250-320 Discharge
  • 100-150 Suction
  • 250-375 Discharge

4. Check Compressor Discharge Temperature


5. Check Air Temperature Rise