TM9T - Flashing Code 7

Article ID: 394
Last updated: 8 Oct, 2020

York Gas Furnace: TM9T

Re: No Heat - Flashing Code 7

Code 7 = Indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out. 

► The furnace will lock out for one hour and then attempt a restart.


Qty Possible Causes:
Dirty Flame Sensor
Bad Glow Plug
Glow Plug Service Letter
1 Clogged Burners
No or Low Gas Pressure
6 Bad Gas Valve


CHECKOUT:

1. Check Ignition Sequence

  • Initiate a call for heat from the thermostat and monitor the ignition sequence.
    • The inducer motor should start with no difficulty.
    • The pressure switch(es) should close within a couple seconds of the inducer starting.
    • The glow plug should energize within 30 seconds of the pressure switch closing.
    • The gas valve should open within 20 seconds of the glow plug energizing.
  • Visually inspect the burners during ignition.

2. Check Glow Plug

  • Look for any visual cracks.
  • Use a meter to test resistance of the glow plug.
    • No Resistance = Bad Glow Plug
  • Start an ignition sequence.
  • Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
    • No Power = Bad Ignition Control
    • Power + No Glow = Bad Glow Plug

3. Check Gas Pressure / Valve

  • Check Gas Valve Power
  • Check for 24VAC between the Yellow and White wires at the gas valve at the point of ignition.
    • No Power = Bad Ignition Control
    • Power + No Ignition ⇒ Check Gas Pressures
  • Check the Inlet Gas Pressure
    • Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
      • Low Pressure = Bad Meter or Regulator
  • Re-apply power to the furnace and activate a call for heat.
  • Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
    • Pressure Drops Below Minimum = Gas Supply Issue
  • Check the Manifold Gas Pressure
  • Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
    • Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
      • No Gas Pressure = Bad Gas Valve
      • Low Gas Pressure ⇒ Attempt to Increase Manifold Gas Pressure
      • Normal Gas Pressure + No (or Delayed) Ignition = Clogged Burners Remove the burners, clean the spreaders, and recheck ignition.

4. Check Flame Sensor

  • On the multi-meter:
    • Switch the test leads to "COM" and "mA".
    • Set the meter on DC 200ù.
    • Check the flame signal when the burners ignite.
      • Normal Reading = 2 to 6 mA
      • Minimum acceptable reading = 1 MicroAmp
        • Low Reading = Dirty Flame SensorClean the Flame Sensor & Re-check
    • CAUTION! Move meter leads back to "COM" and "V" before proceeding!