Knowledgebase

PUDD - Fires then Shuts Off

Article ID: 370
Last updated: 18 Oct, 2017

York Gas Furnace: PUDD

Re: Burners Fire then Shut Off

The furnace goes through a normal ignition sequence, but several seconds after ignition the burners shut off.


Qty Possible Causes (From Most to Least Likely):
2 Dirty flame sensor
Bad Ignition Control
Incomplete Ignition
Pressure Switch Opening
Thermostat Short-Cycling


CHECKOUT:

1. Check Power to Ignition Control

  • Check for 24VAC power between "TH" or "24V" on the ignition control and "C" on the terminal block.
  • Monitor power through the ignition sequence.
    • Power drops out when burners shut off = Pressure Switch Opening or Thermostat Short-Cycling
    • Power stays on but burners shut off --> Step 2. Check Ignition


2. Check Ignition

  • Visually inspect the burners during ignition.
    • Burners should light with little or no delay from the glow plug to the flame sensor.
      • Make sure flame sensor comes in good contact with the flame.
      • Any delay or burners not igniting = Clogged Burners
      • Burners light properly --> Step 3. Check Flame Sensor

3. Check Flame Sensor

  • On the multi-meter:
    • Switch the test leads to "COM" and "mA".
    • Set the meter on DC 200รน.
    • Disconnect the wire from the flame sensor.
    • Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
    • Check the reading when the burners ignite.
      • Minimum acceptable reading = 1 MicroAmp
        • Low Reading --> Clean Flame Sensor & Re-check
        • Normal Reading (2 to 6 mA) but Shuts Off = Bad Ignition Control
    • MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!
This article was:   Helpful | Not helpful
Report an issue
Article ID: 370
Last updated: 18 Oct, 2017
Revision: 1
Access: Public
Views: 17
Comments: 0