Suction Pressure High - Misplaced Guages

Article ID: 23
Last updated: 27 Dec, 2016

Make: All  

Model or Series: All

Type: All

Problem Description:  The suction pressure and head pressure are reading the same.

Observed Symptoms:  

  • Compressor and condenser fan operating.
  • Suction line is hot.
  • Supply air temperature is normal.

Solution:  Suction guage connected to the suction line instead of true suction.


Additional Information: 

  • In the heating mode, both lines are high pressure.
  • All heat pumps should have a "true suction" port that connects to the suction line between the compressor and reversing valve.