Knowledgebase

Climatemaster TT / TS - Water Flow Chart

Article ID: 156
Last updated: 6 Apr, 2017

Climatemaster Geothermal Heat Pumps: TT / TS

Re: Water Flow Chart


Calculate GPM/Ton

TT Coax Water Pressure Drop
Model Pressure Drop (psi) GPM /TON
30° 50° 70° 90°
026 1.5 1.3 1.1 1.0 4.0 2.0
3.1 2.6 2.3 2.1 6.0 3.0
4.1 3.4 3.0 2.7 7.0 3.5
5.1 4.3 3.8 3.4 8.0 4.0
038 1.2 1.0 0.8 0.6 4.0 1.3
2.6 2.5 2.3 2.1 6.0 2.0
4.5 4.2 4.0 3.7 8.0 2.7
5.7 5.2 4.8 4.4 9.0 3.0
049 1.1 0.9 0.8 0.7 5.5 1.4
2.2 2.1 2.0 1.8 8.3 2.1
3.9 3.6 6.2 3.1 11.0 2.8
4.5 4.2 3.8 3.5 12.0 3.0
064 0.5 0.3 0.2 0.1 7.0 1.4
1.9 1.8 1.7 1.6 10.5 2.1
3.9 3.5 3.2 2.9 14.0 2.8
4.8 4.3 3.9 3.5 15.0 3.0
072 1.7 1.5 1.3 1.3 7.5 1.3
3.9 3.4 3.0 2.8 11.3 1.9
6.9 6.0 5.4 5.0 15.0 2.5
8.9 7.7 6.9 6.5 17.0 2.8

TS Coax Water Pressure Drop
Model Pressure Drop (psi) GPM /TON
30° 50° 70° 90°
024 1.5 1.3 1.1 1.0 4.0 2.0
3.1 2.6 2.3 2.1 6.0 3.0
5.1 4.3 3.8 3.4 8.0 4.0
030 1.5 1.3 1.1 1.0 4.0 1.6
3.1 2.6 2.3 2.1 6.0 2.4
5.1 4.3 3.8 3.4 8.0 3.2
036 1.7 1.3 1.1 0.9 4.5 1.5
3.3 3.1 2.9 2.6 6.8 2.3
5.7 5.2 4.8 4.4 9.0 3.0
042 1.1 0.9 0.8 0.7 5.5 1.6
2.2 2.1 2.0 1.8 8.3 2.4
3.9 3.6 6.2 6.1 11.0 3.1
048 1.3 1.1 1.0 0.9 6.0 1.5
2.6 2.5 2.3 2.2 9.0 2.3
4.5 4.2 3.8 3.5 12.0 3.0
060 0.6 0.4 0.3 0.2 7.5 1.5
2.3 2.1 2.0 1.8 11.3 2.3
4.8 4.3 3.9 3.5 15.0 3.0
070 2.4 2.0 1.7 1.6 8.3 1.4
5.2 4.5 4.0 3.8 12.4 2.1
8.0 7.0 6.3 6.0 16.5 2.8

 

 