TM9X/TM9E - Flashing Code 11

Article ID: 734
Last updated: 22 Dec, 2023

York Gas Furnace: TG9S/GY9S

Re: Flashing Code 11

This indicates that a primary or auxiliary limit switch has opened and has remained open for more than five minutes. This condition is usually associated with an air circulation failure. 

Code 11 is a Hard-Lockout which requires cycling 24VAC power to the furnace board to reset (or cycling 115V power).

Qty Possible Causes:
2 Bad ECM Blower Motor
1 Broken Blower Wheel
Bad Control Board
Bad Limit


CHECKOUT:

1. Check Blower Motor/Wheel

  • Turn off power to the furnace.
  • Open the blower access door and check the condition of the blower wheel.
  • Check to see if the motor and wheel turn freely.

2. Check Motor Operation

  • Turn on power to the furnace.
  • Energize a call for "Fan" by jumping "R" to "G".

3. Check Control Board/Motor

  • These furnaces use and X-13 ECM blower motor (constant 120V + 24V speed input on 1,2,3,4 or 5).
  • With power applied to the furnace, check for 120V at the motor high voltage harness between BLK/WHT and WHT.
    • No Power = No Furnace Power or Loose Wiring
    • Power Present ⇒ Continue
  • Check for 24VAC between 24V COM and G on the control board fan outputs.
    • No Power = Bad Control Board ⇒ It may be possible to hook a blower speed to the "EAC" terminal to get temporary fan operation.
    • Power Present + No Blower Operation = Bad Motor, Bad Capacitor or Bad Wiring 

4. Check Limits

  • Check for 24VAC between both sides of the primary limit and "C".
    • Power on Both Sides = Limit Closed
    • Power on One Side Only = Limit Open 
      • Limit Open + Cool Chamber = Bad Limit
  • Alternatively, check for 24VAC between the Red wire on Pin#1 and the Red/Grn wire on Pin#7 of the 12-pin plug.
    • No Power = Limit Closed
    • Power Present = Limit Open