Article ID: 734
Last updated: 22 Dec, 2023
York Gas Furnace: TG9S/GY9S Re: Flashing Code 11 This indicates that a primary or auxiliary limit switch has opened and has remained open for more than five minutes. This condition is usually associated with an air circulation failure. ► Code 11 is a Hard-Lockout which requires cycling 24VAC power to the furnace board to reset (or cycling 115V power).
CHECKOUT: 1. Check Blower Motor/Wheel
This article was:
Helpful |
Not helpful
Report an issue
Article ID: 734
Last updated: 22 Dec, 2023
Revision: 3
Access:
Public
Views: 24
Comments: 0
|
Powered by KBPublisher (Knowledge base software)