Re: Communicating Defrost Board
Fault Code Memory:
- The control stores the 10 most recent fault codes in memory.
- The codes are stored even when power is removed from the control and will remain in memory until they are manually cleared from the control.
- All codes are time stamped and stored in order of occurrence.
- The control stores only one identical fault code during the same series of events. For example, if two or more low temperature cutout faults occur sequentially without another fault occurring in between the low temperature cutout faults, the control only stores the low temperature cutout fault once.
- The stored faults can be displayed by pressing the PUSH BUTTON for two to six seconds, without a call for compressor operation.
Status Code Display |
LED |
Segment 1 |
Segment 2 |
Description |
Off |
|
|
No power to control |
2s on 2s Off |
|
|
Normal operation - No call for compressor |
0.1s On 0.1s Off |
d |
5,4,3,2,1 |
COOLING Short-cycle delay timer |
0.1s On 0.1s Off |
d |
5,4,3,2,1 |
HEATING Short-cycle delay timer |
On |
C |
1 |
COOLING 1st Stg Compressor Operation |
On |
C |
2 |
COOLING 2nd Stg Compressor Operation |
On |
H |
1 |
HEATING 1st Stg Compressor Operation |
On |
H |
2 |
HEATING 2nd Stg Compressor Operation |
On |
A |
1 |
Aux Heat 1 (below BP) |
On |
A |
2 |
Aux Heat 2 (below BP) |
On |
d |
r |
COOLING Demand Response (Utility input) |
On |
d |
r |
HEATING Demand Response (Utility Input) |
On |
E |
1 |
Emergency Heat Stg 1 |
On |
E |
2 |
Emergency Heat Stg 2 |
On |
o |
r |
Oil Return |
On |
d |
d |
Demand Defrost |
On |
d |
c |
Calibration Defrost |
On |
t |
d |
Time & Temperature Defrost |
On |
F |
d |
Forced Defrost |
Operational Fault Codes |
LED |
Segment 1 |
Segment 2 |
Description |
Control Response |
On |
0 |
0 |
Control Failure |
None |
On |
0 |
1 |
High-pressure switch (not in lockout yet) |
None |
2 flash |
0 |
2 |
2 High-pressure faults in 6 hours |
Soft Lockout |
3 flash |
0 |
2 |
4 High-pressure faults in 12 hours |
Hard Lockout |
2 flash |
0 |
3 |
2 DEFROST High-pressure faults in 6 hours |
Soft Lock |
3 flash |
0 |
3 |
4 DEFROST High-pressure faults in 12 hours |
Hard Lockout |
2 flash |
0 |
4 |
Low-pressure switch fault |
Soft Lockout |
3 flash |
0 |
4 |
4 Low-pressure faults in 12 hours |
Hard Lockout |
On |
0 |
5 |
LTCO Active |
None |
On |
0 |
6 |
Low Voltage < 19.2VAC |
None |
On |
0 |
7 |
Low Voltage < 16VAC |
None |
On |
0 |
8 |
Pipe Freeze Protection |
None |
On |
0 |
9 |
Outdoor Sensor shorted in Cooling |
ODF operates at Max |
On |
0 |
9 |
Outdoor Sensor shorted in Heating |
None |
2 flash |
0 |
9 |
Outdoor Sensor shorted in Heating |
Soft Lockout |
On |
1 |
0 |
Outdoor Sensor Open in Cooling |
ODF operates at Max |
On |
1 |
0 |
Outdoor Sensor Open in Heating |
None |
2 flash |
1 |
0 |
Outdoor Sensor Open in Heating |
Soft Lockout |
2 flash |
1 |
1 |
Coil Sensor Shorted |
Soft Lockout |
2 flash |
1 |
2 |
Coil Sensor Open |
Soft Lockout |
2 flash |
1 |
3 |
Discharge Sensor Shorted |
Soft Lockout |
2 flash |
1 |
4 |
Discharge Sensor Open |
Soft Lockout |
On |
1 |
5 |
Discharge Temp > 263 F |
None |
2 flash |
1 |
5 |
Discharge Temp > 263 F (3 times) |
Soft Lockout |
3 flash |
1 |
5 |
Discharge Temp > 263 F (12 times) |
Hard Lockout |
On |
1 |
6 |
Discharge Temp < 90 F |
None |
2 flash |
1 |
6 |
Discharge Temp < 90 F (3 times) |
Soft Lockout |
3 flash |
1 |
6 |
Discharge Temp < 90 F (12 times) |
Hard Lockout |
2 flash |
1 |
7 |
Bonnet Sensor Shorted |
Soft Lockout |
Wiring-related Fault Codes |
LED |
Segment 1 |
Segment 2 |
Description |
Control Response |
2 flash |
1 |
8 |
O Received in A/C Only Mode |
Soft Lockout |
2 flash |
1 |
9 |
W Received in A/C Mode |
Soft Lockout |
2 flash |
2 |
0 |
W & O Received in A/C Mode |
Soft Lockout |
2 flash |
2 |
4 |
W & O Received in H/P Mode |
Soft Lockout |
2 flash |
2 |
5 |
Was A/C Mode, Now H/P Mode |
Operates in A/C Mode |
On |
2 |
6 |
Was H/P Mode, Now A/C Mode |
Operates in Heating |