YZT Status Codes / Fault Codes

York Heat Pump: YZT

Re: Communicating Defrost Board 


Fault Code Memory:


Status Code Display
LED Segment 1 Segment 2 Description
Off No power to control
2s on 2s Off Normal operation - No call for compressor
0.1s On 0.1s Off d 5,4,3,2,1 COOLING Short-cycle delay timer
0.1s On 0.1s Off d 5,4,3,2,1 HEATING Short-cycle delay timer
On C 1 COOLING 1st Stg Compressor Operation
On C 2 COOLING 2nd Stg Compressor Operation
On H 1 HEATING 1st Stg Compressor Operation
On H 2 HEATING  2nd Stg Compressor Operation
On A 1 Aux Heat 1 (below BP)
On A 2 Aux Heat 2 (below BP)
On d r COOLING Demand Response (Utility input)
On d r HEATING Demand Response (Utility Input)
On E 1 Emergency Heat Stg 1
On E 2 Emergency Heat Stg 2
On o r Oil Return
On d d Demand Defrost
On d c Calibration Defrost
On t d Time & Temperature Defrost
On F d Forced Defrost

Operational Fault Codes
LED Segment 1 Segment 2 Description Control Response
On 0 0 Control Failure None
On 0 1 High-pressure switch (not in lockout yet) None
2 flash 0 2 2 High-pressure faults in 6 hours Soft Lockout
3 flash 0 2 4 High-pressure faults in 12 hours Hard Lockout
2 flash 0 3 2 DEFROST High-pressure faults in 6 hours Soft Lock
3 flash 0 3 4 DEFROST High-pressure faults in 12 hours Hard Lockout
2 flash 0 4 Low-pressure switch fault Soft Lockout
3 flash 0 4 4 Low-pressure faults in 12 hours Hard Lockout
On 0 5 LTCO Active None
On 0 6 Low Voltage < 19.2VAC None
On 0 7 Low Voltage < 16VAC None
On 0 8 Pipe Freeze Protection None
On 0 9 Outdoor Sensor shorted in Cooling ODF operates at Max
On 0 9 Outdoor Sensor shorted in Heating None
2 flash 0 9 Outdoor Sensor shorted in Heating Soft Lockout
On 1 0 Outdoor Sensor Open in Cooling ODF operates at Max
On 1 0 Outdoor Sensor Open in Heating None
2 flash 1 0 Outdoor Sensor Open in Heating Soft Lockout
2 flash 1 1 Coil Sensor Shorted Soft Lockout
2 flash 1 2 Coil Sensor Open  Soft Lockout
2 flash 1 3 Discharge Sensor Shorted Soft Lockout
2 flash 1 4 Discharge Sensor Open Soft Lockout
On 1 5 Discharge Temp > 263 F None
2 flash 1 5 Discharge Temp > 263 F (3 times) Soft Lockout
3 flash 1 5 Discharge Temp > 263 F (12 times) Hard Lockout
On 1 6 Discharge Temp < 90 F None
2 flash 1 6 Discharge Temp < 90 F (3 times) Soft Lockout
3 flash 1 6 Discharge Temp < 90 F (12 times) Hard Lockout
2 flash 1 7 Bonnet Sensor Shorted Soft Lockout

Wiring-related Fault Codes
LED Segment 1 Segment 2 Description Control Response
2 flash 1 8 O Received in A/C Only Mode Soft Lockout
2 flash 1 9 W Received in A/C Mode Soft Lockout
2 flash 2 0 W & O Received in A/C Mode Soft Lockout
2 flash 2 4 W & O Received in  H/P Mode Soft Lockout
2 flash 2 5 Was A/C Mode, Now H/P Mode Operates in A/C Mode
On 2 6 Was H/P Mode, Now A/C Mode Operates in Heating