P3DH - Flashing Code 5

Article ID: 544
Last updated: 24 Mar, 2018

York Gas Furnace: P3DH

Re: Flashing Code 5

Flashing Code 5 = Rollout Switch Open

Other symptoms associated with a Code 5:

  • Blower and Inducer Running Continuous
  • No Heat

Qty Possible Causes:
1 Rollout Switch Tripped
Bad Control Board


CHECKOUT:


1. Check Rollout Switches

  • Reset the furnace by cycling power.
  • Start a call for heat by energizing "W".
  • Monitor the LED on the furnace board for lockout indication.
    • If board immediately goes into a Code 5, press the reset button on each Rollout limit and retry.
      • Code 5 Goes Away ⇒ Check for Bad Heat Exchanger
      • Still Code 5 → Step 2. Check Control Board

2. Check Control Board

  • At the control board 12-pin plug:
    • Check for 24VAC between Pin# 11 (BRN) and "C".
    • Check for 24VAC between Pin# 5 (BLK) and "C".
      • Power on One Side Only = Open Limit Circuit ⇒ Check resistance across each roll-out switch.
      • Power on Both Sides + Code 5 = Bad Control Board