TT - Airflow Settings

Article ID: 490
Last updated: 23 Jan, 2018

Climatemaster Geothermal Heat Pumps: TT

Re: Airflow Settings


CFM Board Dip Switch Settings

Tap Setting

Cooling Heating Aux Heat
SW1 SW2 SW3 SW4 SW5 SW6
1 On On On On On On
2 On Off On Off On Off
3 Off On Off On Off On
4 Off Off Off Off Off Off

Airflow Chart

Model Tap Cooling Mode Dehum Mode Heating Mode Aux Ht
Stg1 Stg2 Fan Stg1 Stg2 Fan Stg1 Stg2 Fan
026
 
4 810 950 475 630 740 475 920 1060 475 1060
3 725 850 425 560 660 425 825 950 425 950
2 620 730 370 490 570 370 710 820 370 820
1 520 610 300 - - - 600 690 300 690
038 4 1120 1400 700 870 1090 700 1120 1400 700 1400
3 1000 1250 630 780 980 630 1000 1250 630 1350
2 860 1080 540 670 840 540 860 1080 540 1080
1 730 900 450 - - - 730 900 450 900
049 4 1460 1730 870 1140 1350 870 1560 1850 870 1850
3 1300 1550 780 1020 1210 780 1400 1650 780 1650
2 1120 1330 670 870 1040 670 1200 1430 670 1430
1 940 1120 560 - - - 1010 1200 560 1350
064 4 1670 2050 1020 1300 1600 1020 1860 2280 1020 2280
3 1500 1825 920 1160 1430 920 1650 2050 920 2040
2 1280 1580 790 1000 1230 790 1430 1750 790 1750
1 1080 1320 660 - - - 1200 1470 660 1470
072 4 1620 2190 1050 1270 1650 1050 1690 2230 1050 2230
3 1500 1950 980 1170 1520 980 1600 2100 980 2100
2 1400 1830 910 1100 1420 910 1400 1850 910 1870
1 1320 1700 850 - - - 1240 1620 850 1670