Knowledgebase

P1XU - Flashing Code 3

Article ID: 436
Last updated: 19 Oct, 2020

York Gas Furnace: P1XU

Re: Flashing Code 3

Code 3 = One or More Pressure Switch(es) Open with the Inducer Energized.

  • The P1XU gas furnace has a 2-stage gas valve and 2-speed inducer fan motor.
  • There are two, Dual-Port Pressure Switches which monitor both low and high speed operation of the inducer motor.
    • The low pressure port (-) of both switches goes to the inducer motor and the high pressure (+) goes to the burner compartment (differential pressure).

► This code will go away once the switch(es) close.


Qty Possible Causes:
Bad Inducer Motor
Restricted Vent
Restricted Intake
Water in Inducer
Clogged Drain (Trap)
1 Bad Pressure Switch(es)
1 Water in Pressure Switch / Tubing


CHECKOUT:

1. Check Inducer Motor Operation

  • Start the furnace with a call for heat from the thermostat.
  • Observe and listen to the inducer motor operation.
    • Inducer Motor Starts & Runs Normal → Step 2. Check Pressure Switch
    • Inducer Motor Hums But Does Not Start = Bad Inducer Motor/Capacitor or Item in Inducer Remove inducer & check.
    • Sound of Water "Slurshing" = Water in Inducer  Remove Inducer, pour out water, re-install inducer → Step 3. Check Condensate Drainage
  • Listen for sounds of water in vent piping.
    • If water is gurgling in vent, look for low spots in the vent piping that will hold water.
      • Vent Pipe must have a constant slope back toward the furnace (no traps, sags or droops).

2. Check Pressure Switch

  • The inducer motor starts in Hi Speed (must close 1LP + 2LP), then drops to Low Speed (must close only 1LP).
    • Hi Speed + Code 3 ⇒ Check Both Switches
    • Lo Speed + Code 3 ⇒ Check 1LP Switch
  • Check for 24VAC between each side of the switch and C on the control board.
    • Power on Both Sides = Switch Closed
    • Power on One Side Only = Switch Open ⇒ Check Differential Pressure
  • Use a pressure meter to check the pressure at the switch.
    • Watch for water in the pressure switch hoses.
    • On a two-hose switch, be sure to check "differential pressure" by checking both sides at the same time.
  • Compare actual pressure to the pressure rating on the switch.
    • Pressure Well Above Rating + Switch Open = Bad Switch or Water in Switch
    • Pressure Near or Below Rating = Clogged Drain or Restricted Vent / Intake ⇒ Continue
  • Remove the burner box cover & re-check the pressures.
    • Little or No Improvement = Clogged Drain or Restricted Vent
    • Drastic Improvement = Restricted Intake 
      • Note: It is OK to operate with the burner cover removed as long as there is sufficient combustion air.

3. Check Condensate Drainage

  • Remove each drain hose from the drain trap and check the hose.
    • Water pours out of a hose = Clogged Drain Trap ⇒ Remove and flush the drain trap.
  • Make sure all drain hoses are clear and have a downward slope.
This article was:   Helpful | Not helpful
Report an issue
Article ID: 436
Last updated: 19 Oct, 2020
Revision: 25
Access: Public
Views: 45
Comments: 0