York Gas Furnace: P1XU
Re: No Heat - Flashing Code 7
(Assuming original control board)
Code 7 = Failure to Sense Flame
Qty |
Possible Causes: |
|
Dirty Flame Sensor |
1 |
Bad Glow Plug |
1 |
Clogged Burners |
|
Intake Problem |
|
No or Low Gas Pressure |
|
Bad Gas Valve |
CHECKOUT:
1. Check Ignition Sequence
- Initiate a call for heat from the thermostat and monitor the ignition sequence.
- 1. The inducer motor should start with no difficulty.
- 2. The pressure switch should close within a couple seconds of the inducer starting.
- 3. The glow plug should energize within 30 seconds of the pressure switch closing.
- 4. The gas valve should open within 20 seconds of the glow plug energizing.
2. Check Ignition
- Visually inspect the burners during ignition.
- The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
3. Check Glow Plug
- Look for any visual cracks.
- Use a meter to test resistance of the glow plug.
- No Resistance = Bad Glow Plug
- Start an ignition sequence.
- Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
- No Power = Bad Ignition Control
- Power + No Glow = Bad Glow Plug
4. Check Gas Pressure / Valve
- Check Gas Valve Power
- Check for 24VAC at the gas valve terminals at the point of ignition.
- No Power = Bad Ignition Control
- Power + No Ignition ⇒ Check Gas Pressures
- Check the Inlet Gas Pressure
- Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
- Low Pressure = Bad Meter or Regulator
- Re-apply power to the furnace and activate a call for heat.
- Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
- Pressure Drops Below Minimum = Gas Supply Issue
- Check the Manifold Gas Pressure
- Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
- Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
- No Gas Pressure = Bad Gas Valve
- Low Gas Pressure ⇒ Attempt to Increase Manifold Gas Pressure
- Normal Gas Pressure but No or Delayed Ignition ⇒ Remove the burner compartment cover & recheck ignition.
- Burners Ignite Properly With Cover Off = Intake Problem ⇒ Check for recirculation of the exhaust.
- Burners Still Not Igniting Properly = Clogged Burners ⇒ Remove the burners,clean the spreaders, and recheck ignition.
5. Check Flame Sensor
- On the multi-meter:
- Switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Check the flame signal when the burners ignite.
- Normal Reading = 2 to 6 mA
- Minimum acceptable reading = 1 MicroAmp
- Low Reading = Dirty Flame Sensor ⇒ Clean the Flame Sensor & Re-check
- CAUTION! Move meter leads back to "COM" and "V" before proceeding!