P1XU - Flashing Code 7

Article ID: 393
Last updated: 18 Dec, 2017

York Gas Furnace: P1XU

Re: No Heat - Flashing Code 7

(Assuming original control board)

Code 7 = Failure to Sense Flame


Qty Possible Causes:
Dirty Flame Sensor
1 Bad Glow Plug
1 Clogged Burners
Intake Problem
No or Low Gas Pressure
Bad Gas Valve


CHECKOUT:

1. Check Ignition Sequence

  • Initiate a call for heat from the thermostat and monitor the ignition sequence.
    • 1. The inducer motor should start with no difficulty.
    • 2. The pressure switch should close within a couple seconds of the inducer starting.
    • 3. The glow plug should energize within 30 seconds of the pressure switch closing.
    • 4. The gas valve should open within 20 seconds of the glow plug energizing.

2. Check Ignition

  • Visually inspect the burners during ignition.

3. Check Glow Plug

  • Look for any visual cracks.
  • Use a meter to test resistance of the glow plug.
    • No Resistance = Bad Glow Plug
  • Start an ignition sequence.
  • Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
    • No Power = Bad Ignition Control
    • Power + No Glow = Bad Glow Plug

4. Check Gas Pressure / Valve

  • Check Gas Valve Power
  • Check for 24VAC at the gas valve terminals at the point of ignition.
    • No Power = Bad Ignition Control
    • Power + No Ignition ⇒ Check Gas Pressures
  • Check the Inlet Gas Pressure
    • Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
      • Low Pressure = Bad Meter or Regulator
  • Re-apply power to the furnace and activate a call for heat.
  • Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
    • Pressure Drops Below Minimum = Gas Supply Issue
  • Check the Manifold Gas Pressure
  • Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
    • Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
      • No Gas Pressure = Bad Gas Valve
      • Low Gas Pressure ⇒ Attempt to Increase Manifold Gas Pressure
      • Normal Gas Pressure but No or Delayed Ignition Remove the burner compartment cover & recheck ignition.
        • Burners Ignite Properly With Cover Off = Intake Problem Check for recirculation of the exhaust.
        • Burners Still Not Igniting Properly = Clogged BurnersRemove the burners,clean the spreaders, and recheck ignition.

5. Check Flame Sensor

  • On the multi-meter:
    • Switch the test leads to "COM" and "mA".
    • Set the meter on DC 200ù.
    • Check the flame signal when the burners ignite.
      • Normal Reading = 2 to 6 mA
      • Minimum acceptable reading = 1 MicroAmp
        • Low Reading = Dirty Flame SensorClean the Flame Sensor & Re-check
    • CAUTION! Move meter leads back to "COM" and "V" before proceeding!