Knowledgebase

PHU - Flashing Code 8

Article ID: 317
Last updated: 5 Mar, 2018

York Gas Furnace: PHU

Re: No Heat - Code 8

Code 8 = Flame Lost 5 Times During a Heat Cysle


Qty Possible Causes:
2 Dirty Flame Sensor
Clogged Burners
1 Chattering Pressure Switch
No or Low Gas Pressure
Combustion Air Problem


CHECKOUT:

1. Check Ignition Sequence

  • If the furnace is running, turn the thermostat off and allow the furnace to cool and the blower to stop operating.
  • Initiate a call for heat from the thermostat and monitor the ignition sequence.
    • 1. The inducer motor should start with no difficulty.
    • 2. The pressure switch should close within a couple seconds of the inducer starting.
    • 3. The glow plug should energize within 30 seconds of the pressure switch closing.
    • 4. The gas valve should open within 20 seconds of the glow plug energizing.

2. Check Ignition

  • Visually inspect the burners during ignition.
    • The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
    • Make sure the flame sensor comes in good contact with the flame.

3. Check Glow Plug

  • Look for any visual cracks.
  • Unplug the 2-wire connector to the glow plug.
  • Use a meter to test resistance of the glow plug.
    • No Resistance = Bad Glow Plug
  • Start an ignition sequence.
  • Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
    • No Power = Bad Ignition Control
    • Power Present but No Glow = Bad Glow Plug

4. Check Gas Pressure / Valve

  • Inlet Gas Pressure
  • Turn off power to the furnace and close the gas safety shut-off valve.
  • Hook-up a gas pressure gauge to the inlet test port of the gas valve.
  • Open the gas safety shut-off and check gas pressure.
    • Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
      • Low Pressure = Bad Meter or Regulator
  • Re-apply power to the furnace and activate a call for heat.
  • Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
    • Pressure Drops Below Minimum = Bad Meter/Regulator or Restricted Gas Line
  • Manifold Gas Pressure
  • Turn off power to the furnace and close the gas safety shut-off.
  • Move the gas pressure gauge to the manifold (leaving) test port on the gas valve.
    • CAUTION! Be sure to put the plug back in the inlet test port before proceeding!
  • Open the gas safety shut-off valve and re-apply furnace power.
  • Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
    • Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
      • No Gas Pressure = Bad Gas Valve
      • Low Gas Pressure ⇒ Increase Manifold Gas Pressure
      • Normal Gas Pressure + No or Delayed Ignition = Clogged Burners Remove burners and clean spreaders

5. Check Flame Sensor

  • DO NOT clean flame sensor before checking.
  • On the multi-meter:
    • Switch the test leads to "COM" and "mA".
    • Set the meter on DC 200ù.
    • Check the flame reading when the burners ignite.
      • Normal Reading = 2 to 6 mA
      • Minimum acceptable reading = 1 MicroAmp
        • Low Reading = Dirty Flame SensorClean Flame Sensor & Re-check
        • Normal Flame Reading ⇒ Allow the furnace to operate while monitoring burners and flame sensor.
          • Burners quickly cycle on and off = Chattering Pressure Switch ⇒ Check Pressure Switch
    • CAUTION! Move meter leads back to "COM" and "V" before proceeding!

This article was:   Helpful | Not helpful
Report an issue
Article ID: 317
Last updated: 5 Mar, 2018
Revision: 8
Access: Public
Views: 53
Comments: 0