York Gas Furnace: TM9V 95% 2-Stage, Variable-Speed Gas Furnace
Re: Code 4
Code 4 - Limit Switch Fault
	- Limit Switch is Open (Soft Lockout - will reset when limit closes)
- Opened 5 Times During a Run Cycle (Hard Lokout - auto reset in 1 Hr)
	
		- Roll-Out switches are wired in series with the Primary Limit control and should generate a Code 5, but be aware that a tripped Roll-Out could also generate a Code 4.
- A Blown Fuse on the control board can also generate a Code 4.
 
	
		
			| Qty | Possible Causes: | 
		
			|  | Blower Speed too Low | 
		
			|  | High Gas Pressure | 
		
			|  | Bad Limit | 
		
			|  | Dirty Air Filter | 
		
			|  | Clogged Evaporator Coil | 
		
			|  | Under-sized Ductwork | 
	
CHECKOUT:
1. Check Temperature Rise
	- Start the furnace with a call for heat.
- Ensure that the furnace is running at maximum output (W1 & W2 energized).
- Check and record the return air temperature near the furnace (at the filter if possible) with the blower on.
- Check the supply air temperature (in a straight duct run near the furnace) as the furnace operates.
- Compare the actual temperature rise to the rated temperature rise on the furnace nameplate. (typically 40 - 70 deg.)
	
		- Temperature rise at or above maximum --> Step 2. Check Air Filter
- Temperature rise below maximum --> Suspect Bad Limit
 
2. Check Air Filter
	- Remove air filter and recheck temperature rise.
	
		- Temperature rise drops into normal range = Clogged Air Filter
- Temperature rise still too high --> Step 3. Check Gas Pressure
 
3. Check Gas Pressure
	- De-energize the call for heat and allow the furnace to cool.
- Turn off power to the furnace and close the gas safety shut-off.
- Hook-up a gas pressure gauge to the manifold (leaving) test port on the gas valve.
- Open the gas safety shut-off valve and re-apply furnace power.
- Activate a call for heat and monitor the manifold gas pressure when the gas valve opens.
	
		- Natural Gas = 2.5" w.c. minimum to 3.5" w.c. maximum
- LP Gas = 9" w.c. minimum to 11" w.c. maximum
		
			- Pressure below maximum --> Step 4. Check Blower Speed
- Pressure above maximum --> Adjust Gas Pressure & Re-check Temperature Rise
 
 
4. Check Blower Speed
	- This gas furnace utilizes a variable speed blower motor.
- The blower speed is set with pin settings.
- Refer to the installation instruction for proper fan speed adjustment.
- If possible, increase the Heat blower speed and Re-Check Temperature Rise
5. Check Duct Static Pressure
	- Check the return static pressure (in the blower door if possible).
- Check the supply static pressure (between the furnace and evaporator coil if possible).
	
		- High Duct Static = Above 0.5" w.c.
		
			- High Return Static + Low Supply Static = Restricted Return Ductwork
- Low Return Static + High Supply Static = Clogged Coil or Restricted Supply Ductwork
			
				- Compare static on both sides of evaporator coil.
				
					- High Static Entering Coil + Low Static Leaving Coil = Clogged Coil