YHJF60 Add-On Heat Pump - Low Heat When Cold

Article ID: 118
Last updated: 6 Nov, 2020

YHJF60 Add-On Heat Pump

Re: Low Heat When Cold Outside

Unlike all other sizes of the YHJF Heat Pump, the 5 Ton model has a 2-Stage compressor and a YorkGuard VI module.

In an Add-On Heat Pump application, the YorkGuard VI module uses its Outdoor Ambient Sensor and a field-installed Bonnet Sensor (mounted between the furnace & indoor coil) to control "Fossil Fuel" operation.


Qty Possible Causes:
1 Gas Furnace not Operating
YorkGuard Mis-Configured or Mis-Wired
Thermostat Mis-Configured
2-Stage Furnace not Running 2nd Stage
Bad Ambient Sensor
Gas Furnace Under-Sized

CHECKOUT:

1. YorkGuard VI - "Fossil Fuel" Sequence of Operation

For Fossil Fuel Operation, the following setting must be made on the YorkGuard:

  • FFUEL = Set to "On"
  • BP = Set for 45, 40 or 35 deg.
  • LTCO = Set for 20, 15 or 10 deg.
  • Bonnet Sensor installed & wired to "BS" and "BSG"

2. Outdoor ABOVE Balance Point (BP)

  • On a call for "Y1" the YorkGuard energizes the compressor for 1st Stage heating.
  • On a call for "Y2" the YorkGuard energizes the compressor unloading solenoid to put the compressor in full operation.
    • The YorkGuard also energizes "Y2 Out" to tell the variable speed indoor fan to go to "High Heat" speed.
  • On a call for "W" (or "Aux") the YorkGuard will keep Aux Heat outputs "W1 Out" and "W2 Out" de-energized.
    • If the heat pump goes into a Lockout condition, the YorkGuard will automatically energize "W1 Out" to satisfy heating demand.

3. Outdoor BELOW Balance Point (BP)

  • On a call for "Y1" the YorkGuard energizes the compressor for 1st Stage heating.
  • On a call for "Y2" the YorkGuard energizes the compressor unloading solenoid to put the compressor in full operation.
    • The YorkGuard also energizes "Y2 Out" to tell the variable speed indoor fan to go to "High Heat" speed.
  • On a call for "W" (or "Aux") the YorkGuard will energize "W1 Out" to start the furnace while keeping the compressor operating.
    • The compressor continues to operate until the Bonnet Sensor temperature reaches 90 deg.
      • If the furnace fails to operate the heat pump will continue to operate to try to maintain heating.

4. Outdoor BELOW LTCO

  • The YorkGuard basically enters Emergency Heat mode.
  • On a call for "Y1" the YorkGuard keeps the compressor off and energizes "W1 Out" to start the gas furnace.