YHJF60 Add-On Heat Pump Re: Low Heat When Cold Outside Unlike all other sizes of the YHJF Heat Pump, the 5 Ton model has a 2-Stage compressor and a YorkGuard VI module. In an Add-On Heat Pump application, the YorkGuard VI module uses its Outdoor Ambient Sensor and a field-installed Bonnet Sensor (mounted between the furnace & indoor coil) to control "Fossil Fuel" operation.
CHECKOUT: 1. YorkGuard VI - "Fossil Fuel" Sequence of Operation For Fossil Fuel Operation, the following setting must be made on the YorkGuard:
2. Outdoor ABOVE Balance Point (BP)
3. Outdoor BELOW Balance Point (BP)
4. Outdoor BELOW LTCO