        York P3UR Furnace - Data
          York Gas Furnace: P3UR   Re: Physical Data         Model   AFUE   Temp Rise   Motor   Blower       40   92.4%   35-65 deg.   1/3 hp   10x6       60   92.2%   45-75 deg.   1/3 hp   10x6       80   92%   35-65 deg.   1/2 hp   11x8       80   94.3%   30-60 deg.   3/4 hp   11x8       100   92.2%  ... 
        
        
        14 Feb, 2018
        
        
        
        Comments: 0
        
     
    	 
        PUR - Diagnostic/Fault Codes
          York Gas Furnaces: P3URC   Re: Diagnostic/Lockout Codes   This York gas furnaces has a control board inside the furnace blower compartment that will flash a diagnostic code that shows the operating status of the furnace.         Diagnostic Codes:       Steady On Red   Control failure         ... 
        
        
        14 Feb, 2018
        
        
        
        Comments: 0
        
     
    	 
        P3UR - No Heat Call - Heat is Operating
          York Gas Furnace: P3UR   Re: No Heat Call - Heat is Operating   The customer called and reported a, "No Heat" but when the technician arrived the system was operating.    There are (2) Furnace Faults that will Auto-Reset after 1-Hour*:      Code 6 = Multiple Pressure Switch Openings   Code 7 =... 
        
        
        17 Nov, 2020
        
        
        
        Comments: 0
        
     
    	 
        Gas Furnace - Blown Low Voltage Fuse
          Gas Furnace   Re: Blown Low Voltage Fuse   The low voltage fuse provides protection for the control board and other low voltage components in the case of high amperage caused by a low voltage short or excess component load.    ► The fuse must be sized per the "VA" of the transformer.    Amps = VA... 
        
        
        19 Apr, 2018
        
        
        
        Comments: 0
        
     
    	 
        P3UR - Flashing Code 2
          York Gas Furnace: P3UR / P3DH   Re: Flashing Code 2   Code 2 = Pressure switch stuck closed   The furnace pressure switch should only close when the inducer fan output is energized. If control board is not energizing the inducer fan output and the pressure switch circuit is closed, the board will... 
        
        
        10 Jan, 2022
        
        
        
        Comments: 0
        
     
    	 
        P3UR - Flashing Code 3
         York 90% Gas Furnace: P3UR  Re: Flashing Code 3  Code 3 = Furnace Pressure Switch failed to close on a call for heat.          Qty   Possible Causes:       2   Bad Inducer Motor       1   Bad Pressure Switch       1   Clogged / Frozen Drain       1   Pressure Hose Problem       2   Item Stuck in... 
        
        
        16 Oct, 2024
        
        
        
        Comments: 0
        
     
    	 
        P3UR - Flashing Code 6
         York 90% Gas Furnace: P3UR  Re: Flashing Code 6  Code 6 = Multiple Pressure Switch Openings on a call for heat.          Qty   Possible Causes:          Water in the vent (improper slope)          Water in inducer (clogged drain)          Restricted Intake       1   Bad Pressure Switch       1  ... 
        
        
        17 Nov, 2020
        
        
        
        Comments: 0
        
     
    	 
        P3UR - Flashing Code 7
         York Gas Furnace: P3UR  Re: No Heat - Code 7  (Assuming original control board)  Code 7 = Failure to Sense Flame          Qty   Possible Causes:       2   Dirty Flame Sensor       2   Bad Glow Plug          Clogged Burners       1   No or Low Gas Pressure          Bad Gas Valve          CHECKOUT: ... 
        
        
        7 Jan, 2019
        
        
        
        Comments: 0
        
     
    	 
        Gas Furnace - Making Noise - Heating
          Gas Furnace   Re: Making Loud Noise While Heating    Noises from equipment can be very difficult to identify unless something is obviously broken.  Be sure to work with the customer to identify the noise they are hearing.           Qty   Possible Causes:       1   Bad Inducer Motor          Bad... 
        
        
        17 Mar, 2017
        
        
        
        Comments: 0
        
     
    	 
        Gas Furnace - Blower Motor Not Running
          Gas Furnace   Re: Blower Motor Not Running    The furnace control board energizes the fan motor through line-voltage outputs for both heating and cooling.   There are two fan speed outputs on the control board: Cool and Heat    On a call for cooling "Y", the control board should immediately... 
        
        
        18 Apr, 2017
        
        
        
        Comments: 0
        
     | 