GSH/GSV 2 THRU 5 TON Performance Chart

Article ID: 601
Last updated: 15 Feb, 2019

Climatemaster Geothermal: GSH024 / GSV024

Re: Performance Chart

The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF and operating at FULL CAPACITY.

► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.


COOLING

EWT Suction Discharge Superheat Subcool Water Rise Air Drop
50° 73-84 115-142 12-20 8-16 8-15 20-25
70° 73-84 158-186 9-16 8-14 8-15 19-24
90° 73-84 208-241 9-17 8-14 7-17 17-23
110° 75-86 260-310 8-15 10-24 5-13 15-20


HEATING

EWT Suction Discharge Superheat Subcool Water  Drop Air  Rise
30° 37-46 172-196 12-16 1-4 3.4-5.6 15-22
50° 53-65 185-220 10-17 1-5 5.1-8.1 24-31
70° 73-88 210-242 14-19 1-5 6.7-9.0 30-38
90° 90-105 225-270 18-28 2-5 7.2-12.4 33-42