Climatemaster Geothermal: GSH024 / GSV024
Re: Performance Chart
The following chart shows the design operating conditions of the heat pump WITH THE HWG OFF and operating at FULL CAPACITY.
► The chart is based on 3 GPM/Ton and 70° Return Air Temperature.
COOLING
EWT | Suction | Discharge | Superheat | Subcool | Water Rise | Air Drop |
50° | 73-84 | 115-142 | 12-20 | 8-16 | 8-15 | 20-25 |
70° | 73-84 | 158-186 | 9-16 | 8-14 | 8-15 | 19-24 |
90° | 73-84 | 208-241 | 9-17 | 8-14 | 7-17 | 17-23 |
110° | 75-86 | 260-310 | 8-15 | 10-24 | 5-13 | 15-20 |
HEATING
EWT | Suction | Discharge | Superheat | Subcool | Water Drop | Air Rise |
30° | 37-46 | 172-196 | 12-16 | 1-4 | 3.4-5.6 | 15-22 |
50° | 53-65 | 185-220 | 10-17 | 1-5 | 5.1-8.1 | 24-31 |
70° | 73-88 | 210-242 | 14-19 | 1-5 | 6.7-9.0 | 30-38 |
90° | 90-105 | 225-270 | 18-28 | 2-5 | 7.2-12.4 | 33-42 |