GSV/GSH - Flashing Code 4 (Heating)

Article ID: 551
Last updated: 8 Feb, 2023

ClimateMaster Heat Pump: Heating

Re: Code 4 / LT1 Fault

Code 4 = Low Water Coil Temperature (FP1)

  • The FP1 thermistor temperature must be below the selected low temperature limit setting* for 30 continuous seconds during a compressor run cycle to be recognized as a FP1 fault.
    • *JW3 Clipped = 10 deg. Unclipped = 30 deg.
  • The FP1 input is bypassed for the initial 120 seconds of a compressor run cycle.
  • FP1 is set at the factory for one try. Therefore, the control will go into lockout mode once the FP1 fault has occurred.

Qty Possible Causes:
1 JW3 Not Clipped
4 Low Refrigerant Charge
1 Expansion Valve Underfeeding
Low Water Flow
Bad FP1 Sensor

CHECKOUT:

1. Check JW3 Jumper

  • The JW3 jumper on the control board should be clipped in all applications with ground well piping.
  • Locate the JW3 jumper on the board and confirm that it is clipped.
    • Not Clipped ⇒ Turn off power to the unit and clip the jumper.

2. Check Operating Conditions

  • Set the thermostat to call for heat and ensure that the unit is running at full capacity (Y1 & Y2 Energized).
  • Unplug the 3-wire heater connector from the control board to prevent aux heater operation.
  • Allow the unit to operate for at least 5 minutes.
  • Check and record the HWG Inlet and Outlet Temperatures (if present).
    • Cold HWG temperatures drastically affect operating conditions and can cause excessive unit operation.
    • Make sure bottom heating element of water heater is operational and thermostat is set for approx. 120 deg.
  • Unplug the HWG pump motor (if the HWG piping hooked-up and active).
  • Check and record the Water Pressure Drop through the geo-thermal unit.
  • Check and record the Entering Water Temperature and the Leaving Water Temperature.
  • Check and record Refrigerant Pressures.
  • Check and record the Air Temperature Rise through the unit.

► Be sure to re-connect the 3-wire heater plug and HWG pump before closing the unit.


3. Compare to Unit Performance Chart

  • Use Flow Sheet to convert pressure drop to GPM and then GPM per Ton.
  • Compare actual conditions to Unit Performance Chart.