Goodman Gas Furnace: GMS8/GDS8/GHS8
Re: Code 1 / Won't Ignite
Code 1 = 3 Failed Ignition Attempts
Qty |
Possible Causes: |
|
Dirty Flame Sensor |
2 |
Bad Ignitor |
1 |
Bad Control Board |
|
Tripped Auxiliary Limit |
|
Bad Gas Valve |
CHECKOUT:
1. Check Ignition Sequence
- If necessary, reset the furnace lockout by cycling high voltage or low voltage power.
- Initiate a call for heat from the thermostat and monitor the ignition sequence.
- The inducer motor should start with no difficulty.
- The pressure switch should close within a couple seconds of the inducer starting.
- The glow plug should energize within 30 seconds of the pressure switch closing.
- The gas valve should power and open within 20 seconds of the glow plug energizing.
- Check for 24VAC across the two wires at the gas valve.
2. Check Ignition
- Visually inspect the burners during ignition.
- The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
3. Check Glow Plug
- Look for any visual cracks.
- Test resistance of the glow plug.
- No Resistance = Bad Glow Plug
- Start an ignition sequence.
- Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
- No Power = Bad Ignition Control
- Power Present + No Glow = Bad Glow Plug
4. Check Control Board Output
- Re-start the furnace with a call for heat from the thermostat.
- Ensure that the glow plug energizes.
- At the point of ignition, check for 24VAC between Terminal 9 (Blue) and Terminal 12 (Brown) of the molex plug on the control board.
- No Power = Bad Control Board
- Power at Board + No Power at Gas Valve = Tripped Auxilairy Limit (Mounted in blower compartment) ⇒ Check blower operation.
5. Check Gas Pressure / Valve
- Inlet Gas Pressure
- Turn off power to the furnace and check the inlet gas pressure.
- Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
- No or Low Pressure = Bad Meter or Regulator
- Normal Pressure ⇒ Continue
- Re-apply power to the furnace and activate a call for heat.
- Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
- Pressure Drops Below Minimum = Bad Meter/Regulator or Restricted Gas Line
- Normal Pressure ⇒ Check Manifold Gas Pressure
- Manifold Gas Pressure
- Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
- Normal Pressure = 2.5 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
- No Gas Pressure = Bad Gas Valve
- Low Gas Pressure ⇒ Increase Manifold Gas Pressure
- Normal Gas Pressure + No or Delayed Ignition = Clogged Burners ⇒ Remove burners and clean spreaders
6. Check Flame Sensor
- DO NOT clean the flame sensor before testing!
- On the multi-meter:
- Switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Check the reading when the burners ignite.
- Minimum acceptable reading = 1 MicroAmp
- Low Reading ⇒ Clean Flame Sensor & Re-check
- Normal Reading (2 to 6 mA) but Shuts Off = Bad Control Board
- MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!