Knowledgebase

GMH95 / GCH9 - Flashing Code 3

Article ID: 432
Last updated: 17 Dec, 2024

Goodman Gas Furnace: GMH95 / GCH9

Re: Flashing Code 3

Code 3 = Pressure Switch failed to close with the inducer energized.

► There are 2 Pressure Switches in the furnace.  Only the Inducer Pressure Switch will cause a Code 3. The Drain Pressure Switch (labeled as Front Cover Switch) breaks power to the gas valve.

► The diagnostic code will go away once the pressure switch closes.


Qty Possible Causes:
1 Bad Inducer Motor
3 Bad Pressure Switch
Item Stuck in Inducer Motor
Bad Inducer Blower Wheel
Bad Ignition Control


CHECKOUT:

1. Check Control Board / Inducer Motor

  • Start the furnace with a call for heat.
    • Inducer motor should start within 15 seconds.
      • Inducer motor starts & runs normally → Step 2. Check Pressure Switch
      • Inducer motor hums but does not start = Bad Inducer Motor or Item in Inducer ⇒ Remove inducer & check
      • Inducer motor does not attempt to start & shows Code 3  Check for 115V power to inducer.
        • Power + No Inducer = Bad Inducer Motor
        • No Power = Bad Control Board

2. Check Pressure Switch

  • Switch Contacts
  • Check for 24VAC between each side of the pressure switch (YEL) to C and (Org) to C.
    • Power on One Side Only = Switch Open ⇒ Check Switch Pressure
    • Power on Both Sides + Code 3 = Bad Control Board
  • Switch Pressure
  • Use a pressure meter to check the pressure at the switch.
  • Compare actual pressure to pressure rating on the switch.
    • Pressure Near or Below Rating = Blocked/Restricted Vent or Bad Inducer Blower Wheel
    • Pressure Well Above Rating + Switch Not Closed = Bad Switch 

This article was:   Helpful | Not helpful
Report an issue
Article ID: 432
Last updated: 17 Dec, 2024
Revision: 12
Access: Public
Views: 126
Comments: 0