Article ID: 432
Last updated: 17 Dec, 2024
Goodman Gas Furnace: GMH95 / GCH9 Re: Flashing Code 3 Code 3 = Pressure Switch failed to close with the inducer energized. ► There are 2 Pressure Switches in the furnace. Only the Inducer Pressure Switch will cause a Code 3. The Drain Pressure Switch (labeled as Front Cover Switch) breaks power to the gas valve. ► The diagnostic code will go away once the pressure switch closes.
CHECKOUT: 1. Check Control Board / Inducer Motor
This article was:
Helpful |
Not helpful
Report an issue
Article ID: 432
Last updated: 17 Dec, 2024
Revision: 12
Access:
Public
Views: 126
Comments: 0
|
Powered by KBPublisher (Knowledge base software)