A/C - Blown Fuse / Low Voltage Short

Article ID: 297
Last updated: 24 May, 2017

Air Conditioner

Re: Blown Fuse / Low Voltage Short

Indications: A Blown Low Voltage Fuse or a Bad Transformer on the Furnace or Air Handler


Qty Possible Causes:
  Shorted Control Wire To Stat
1 Shorted Control Wire To A/C
Bad Contactor
Shorted Pressure Switch Wiring
Bad Furnace Board
Bad ECM Blower Motor
Bad Thermostat

CHECKOUT:

1. Install Mini-Breaker

  • Turn off line-voltage power to the air handler or furnace.
  • Remove the blown fuse.
  • Install a resettable low voltage breaker (if not already on the transformer) in the fuse holder.

2. Isolate the Thermostat

  • At the furnace or air handler, disconnect the control wiring to the thermostat. (Leave all other low voltage wiring connected.)
  • Turn line-voltage power back on to the furnace or air handler.
    • No Short --> Step 3. Test A/C Wiring
    • Short --> Disconnect R control wire at the outdoor unit & retest.
      • No Short = Bad Defrost Board or Shorted Sensor
      • Short = Shorted Control Wire to H/P

3. Test A/C Wiring

At the Furnace or Air Handler, use a jumper wire to test each output as follows:

  • Connect R to G = Energize fan relay.
    • No Short --> Proceed to next test.
    • Short --> Disconnect the low voltage wiring to the motor & retest.
      • No Short = Bad ECM Motor
      • Short = Bad Air Handler Board
  • Connect R to Y = Energize compressor. (Wait until compressor contactor energizes.)
    • No short --> Proceed to next test.
    • Short --> Disconnect Y control wire at outdoor unit & retest.
      • Short = Shorted Control Wire to A/C
      • No Short --> Re-connect the Y control wire, disconnect the Y wire from the contactor and retest.
        • No Short = Bad Contactor 
        • Short = Shorted Pressure Switch Wiring

4. Test Thermostat

  • Turn off line-voltage power to the furnace or air handler.
  • Re-connect the control wiring to the thermostat.
  • Set the thermostat System switch to "Off" and the Fan switch to "Auto".
  • Turn on line-voltage power to the air handler.
    • No short --> Step 5. Test Thermostat Wiring
    • Short --> Remove the thermostat from the sub-base and retest.
      • No Short = Bad or Mis-Wired Thermostat
      • Short = Shorted Control Wire to Stat

5. Test Thermostat Wiring

  • At the Air Handler, use a jumper wire to test each output as follows:
    • R to G going to the stat.
    • R to Y going to the stat.
      • No Short --> Suspect an Intermittent Short in Control Wiring - Trace the control wires & look for spots where control wiring contacts metal.
      • Short On Any Wire= Shorted Control Wire to Stat