Goodman Gas Furnace: GMPN
Re: Code 1 / Won't Ignite
Code 1 = 3 Failed Ignition Attempts
Qty |
Possible Causes: |
3 |
Tripped or Bad Rollout (Bad Heat Exchanger) |
1 |
Dirty Flame Sensor |
4 |
Bad Ignitor |
1 |
Bad Control Board |
|
Tripped or Bad Stack Over-Temp Switch |
|
Bad Gas Valve |
1 |
Excessive Inlet Gas Pressure |
CHECKOUT:
1. Check Ignition Sequence
- If necessary, reset the furnace lockout by cycling high voltage or low voltage power.
- Initiate a call for heat from the thermostat and monitor the ignition sequence.
- The inducer motor should start with no difficulty.
- The pressure switch should close within a couple seconds of the inducer starting.
- The glow plug should energize within 30 seconds of the pressure switch closing.
- The gas valve should power and open within 20 seconds of the glow plug energizing.
- Check for 24VAC across the two wires at the gas valve.
2. Check Ignition
- Visually inspect the burners during ignition.
- The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
3. Check Glow Plug
- Look for any visual cracks.
- Test resistance of the glow plug.
- No Resistance = Bad Glow Plug
- Start an ignition sequence.
- Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
- No Power = Bad Ignition Control
- Power Present + No Glow = Bad Glow Plug
4. Check Control Board Output
- Re-start the furnace with a call for heat from the thermostat.
- After the glow plug starts to heat-up, check for 24VAC from terminal 7 (Purple) of the molex plug on the control board to ground.
- Approximately 15 - 20 seconds after powering the glow plug, the control board should send 24VAC power out terminal 7 to the gas valve.
- No Power = Bad Control Board
- Power at Board + No Power at Gas Valve = Tripped Limit ⇒ Check each manual-reset Roll-Out Limit (around the burners) and the Stack Limit (vent outlet).
- If a roll-out is tripped, suspect and check for a Bad Heat Exchanger.
- If the Stack Limit is tripped, suspect a Clogged or Restricted Vent.
5. Check Gas Pressure / Valve
- Inlet Gas Pressure
- Turn off power to the furnace and check the inlet gas pressure.
- Minimum Pressure = 5" w.c. for Nat. gas, and 11" w.c. for propane.
- Maximum Pressure = 15" w.c. (Excessive pressure may lock the gas valve closed).
- Low Pressure = Bad Meter or Regulator
- High Pressure = Bad or Wrong Regulator
- Re-apply power to the furnace and activate a call for heat.
- Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
- Pressure Drops Below Minimum = Bad Meter/Regulator or Restricted Gas Line
- Manifold Gas Pressure
- Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
- Normal Pressure = 3 - 3.5" w.c. for Nat. Gas, 9 - 11" w.c. for LP
- No Gas Pressure = Bad Gas Valve or Excessive Inlet Gas Pressure
- Low Gas Pressure ⇒ Increase Manifold Gas Pressure
- Normal Gas Pressure but No or Delayed Ignition = Clogged Burners ⇒ Remove burners and clean spreaders
6. Check Flame Sensor
- DO NOT clean the flame sensor before testing!
- On the multi-meter:
- Switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Check the reading when the burners ignite.
- Minimum acceptable reading = 1 MicroAmp
- Low Reading ⇒ Clean Flame Sensor & Re-check
- Normal Reading (2 to 6 mA) but Shuts Off = Bad Control Board
- MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!