York Heat Pump: Heating
Re: High Pressure Fault - Last Mode Heat Pump
The heat pump was running in normal heat mode (not in defrost) and the high pressure switch tripped.
A High Pressure Lockout is indicated by the following LED pattern on the outdoor unit control board:
- Green = Off
- Red = 2 Flashes
X/L Output
- 2 Flashes at Thermostat = Soft Lockout
- Switch opened two times in 6 hours.
- Reset by cycling thermostat or jumping Test pins.
- 3 Flashes at Thermostat = Hard Lockout
- Four Soft Lockouts in 12 hours.
- Reset by cycling 24VAC power to the board.
Qty |
Possible Causes: |
1 |
Refrigerant OverCharge |
1 |
Bad Expansion Valve |
1 |
Bad Blower Motor / Capacitor |
|
Bad CFM Board |
|
Low Indoor Airflow |
|
Refrigerant Restriction |
|
Bad Pressure Switch |
CHECKOUT:
1. Check Indoor Airflow
- Set the thermostat to call for heat.
- Confirm that the indoor fan is operating and air is blowing out of the supply registers
2. Check Blower Motor
- The YZE & YZH heat pumps should be matched with a Variable Speed Indoor Blower.
- At the air handler, confirm that 240VAC is being supplied to the motor.
- Confirm that 24VAC is present between "C" and "G", "Y1" or "Y2".
- No 24VAC power = No signal from thermostat
- 240V Power Present + 24V Power Present + No Blower Operation = Bad Blower Motor or Bad CFM Board
3. Check Refrigerant Pressures
- If the heat pump is in lockout (still flashng a code), reset by removing 24VAC power to the outdoor control board (remove "R" or cycle power to the air handler).
- Initiate a call for heat from the thermostat.
- Hook-up refrigerant gauges to the pressure ports on the unit.
- Blue --> "True Suction" Low Pressure
- Red --> High Pressure (either refrigerant line)
- Place an insulated temperature probe on the liquid line between the evaporator coil & O/D expansion valve.
- Allow the unit to run for at least 10 minutes.
- Monitor pressures and temperature as the system operates.
- If pressure exceeds Normal Range or kicks-off on Hi Pressure safety in the first 5 minutes = Bad Overcharge or No Indoor Blower → Step 6. Check Air Filter & Indoor Coil
- If the compressor never kicks on & the control locks-out on Hi Pressure ⇒ Suspect a Bad Pressure Switch
4. Check Sub-Cooling
- Record "Saturation Temperature" from the discharge pressure gauge.
- Subtract the Actual liquid line temperature reading.
- Saturation Temp - Liquid Line Temp = Sub-Cooling
- Sub-Cooling > 13 deg. + High Discharge + High Suction = Overcharged
- Sub-Cooling > 13 deg. + High Discharge + Low Suction = Bad Expansion Valve
- Sub-Cooling < 2 deg. + High Discharge = Low Indoor Heat Transfer → Step 5. Check Heat Pump Temperature Rise
5. Check Heat Pump Temperature Rise
- Check to make sure the indoor fan is operating.
- Disconnect auxiliary heat (remove "W" at the air handler or thermostat).
- Check the Return Air Temperature at the air handler (at the filter if possible).
- High Return Air Temperature (more than 85 deg.) = Heat Recycling
- Check the Supply Air Temperature near the air handler (in a straight duct run if possible).
- Calculate the Temperature Rise = Supply Air Temperature - Return Air Temperature
- Normal Heat Pump Temperature Rise = 15 - 20 deg.
6. Check Air Filter & Indoor Coil
- Remove Air Filter and Check for a Dirty Indoor Coil
- If Indoor Coil is OK ⇒ Re-Check Temperature Rise with the filter removed.
- No Change = Restricted Ductwork or Low Blower Speed → Step 7. Check Duct Static Pressure
- Temperature Rise Becomes Normal = Clogged Air Filter ⇒ Replace Filter & Re-check Pressures
7. Check Duct Static Pressure
- Check the return static pressure (between the air handler and filter if possible).
- Check the supply static pressure.
- High Static = Above 0.5" w.c.
- High Return Static + Low Supply Static = Restricted Return Ductwork
- Low Return Static + High Supply Static = Restricted Supply Ductwork
- Static Pressure Normal ⇒ Increase Blower Speed or Clean Blower Wheel