GMP Gas Furnace - Kicking On and Off

Article ID: 229
Last updated: 4 Dec, 2020

Goodman Gas Furnace: GMP

Re: Furnace Cycles Off and On

The gas furnace occasionally kicks off and then re-fires.


Qty Possible Causes:
Pressure Switch Fault
Primary Limit Switch Open
1 Low Flame Signal
Bad Control Board
Thermostat Issue

CHECKOUT:

1. Check Diagnostic Indication

  • Try to catch the furnace cycling-off & check the diagnostic indication on the control board.
  • Furnace Cycling Off and No Diagnostic = "W" Dropping Out, Low Flame Signal or Bad Control Board
    • Place a jumper between "R" and "W" and re-check.
      • Furnace Runs Normally = Thermostat Issue
      • Furnace Still Cycles & No Fault Indication = Low Flame Signal or Bad Control Board Step 4. Check Flame Sensor

2. Check Pressure Switch

  • Monitor for 24VAC between the two "Yellow" wires attached to the pressure switch when the furnace shuts off.
  • Check the rated pressure of the switch.
  • Place a pressure gauge in-line with the pressure switch hose.
  • Monitor the pressure as the furnace operates.
    • Pressure at or near the rating and the switch opens = Restricted Vent or Inducer
    • Pressure well above the rating and the switch opens = Bad Pressure Switch

3. Check Limit Switch

  • Monitor for 24VAC between the two "Red" wires attached to the limit switch when the furnace shuts off.
  • Check the rated temperature rise on the furnace nameplate.
  • Monitor the temperature rise as the furnace operates.
    • Temperature rise at or above rating and limit opens = Low Airflow or Over-Fired
    • Temperature below rating and limit opens = Bad Limit

4. Check Flame Sensor

  • DO NOT CLEAN THE FLAME SENSOR BEFORE TESTING.
  • On the multi-meter:
    • Switch the test leads to "COM" and "mA".
    • Set the meter on DC 200ù.
    • Disconnect the wire from the flame sensor.
    • Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
    • Check the reading when the burners ignite.
      • Minimum acceptable reading = 1 MicroAmp
        • Low Reading ⇒ Clean Flame Sensor & Re-check
        • Normal Reading (2 to 6 mA) but Shuts Off = Bad Ignition Control
    • MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!