York Heat Pump: Yorkguard VI
Re: Low Discharge Temperature (Cooling)
The status lights on the module will indicate as follows: Red = On, Green = 6 Flash.
- If, after energizing the compressor contactor for 1 hour, the Yorkguard module senses a compressor discharge temperature lower than 90 deg. the unit will enter a Low Discharge Temperature lockout which disables compressor operation.
- This code is intended to indicate a compressor not operating, but other issues that may result in a low compressor discharge reading are often the cause.
Qty |
Possible Causes: |
|
Tripped Breaker |
|
Bad Capacitor |
|
Bad Compressor |
|
Bad Contactor |
|
Burnt Compressor Terminals |
|
Bad Discharge Sensor |
1 |
Bad Indoor Expansion Valve |
CHECKOUT:
1. Check Outdoor Unit
- Make sure the thermostat is set correctly and calling for Cool.
- Remove the access panel of the outdoor unit.
- Check for 230V inlet power on the compressor contactor.
2. Check Breaker & Compressor
- Pull the service disconnect switch.
- Check resistance between each leaving leg of the compressor contactor & ground.
- Any resistance = Electrical Short --> Check Compressor
- No Short --> Check Capacitor
- Check the unit breaker at the breaker panel and reset if necessary.
- Re-insert the service disconnect plug to restore power to the outdoor unit.
- Re-check for 230V on the contactor inlet.
3. Check Contactor
- Contactor pulled-in but no compressor operation:
- Check for 230V across the leaving legs of the compressor contactor.
- Inlet Power + No (or low) Outlet Power = Bad Contactor
- Inlet Power + Outlet Power + No Compressor = Compressor off on Internal Overload or Burnt Compressor Terminals
4. Check Pressures & Temperatures
- Turn off power to the outdoor unit by pulling the service disconnect or turning off the breaker.
- Hook-up refrigerant gauges to the pressure ports on the unit.
- Blue --> "True Suction" Low Pressure
- Red --> High Pressure (liquid line)
- Re-apply power to the outdoor unit.
- Start the compressor with a call for cooling from the thermostat.
- Allow the system to operate for at least 5 - 10 minutes.
- Observe refrigerant pressures.
- Normal R-22 Pressures = 55 to 80 psig Suction, 150 to 270 psig Head.
- Normal R410A Pressures = 100 to 150 psig Suction, 200 to 400 psig Head.
- Hook an insulated thermistor to the compressor discharge line and check temperature.
- Normal discharge temperature = 130 to 160 deg.
- Discharge Temperature Below 100 deg. --> Contact Supervisor
5. Check Discharge Sensor
- Pull the service disconnect switch.
- Remove the discharge sensor wires from the board.
- Set the mulit-meter for 200K Ohms.
- Check the resistance across the sensor (see York Sensor Resistance Chart).
- Compare the sensor temperature to the actual compressor discharge temperature.
- Replace sensor if necessary.
► If necessary, you can disable the discharge temperature sensor and the associated fault codes. (Confirm with Supervisor first.)
- Power off the Yorkguard VI by disconnecting the "R" wire.
- Disconnect the two discharge sensor wires from the Yorkguard board (tape-off the ends).
- Re-power the board by re-connecting the "R" wire.