Amana Gas Furnace; GUC/GUX
Re: Flashing Code 1
- If a flame was not sensed during the first 7 seconds after the gas valve was energized, the control turns off the gas.
- The control will make 3 tries before it determines that it cannot establish measureable combustion and enters a lockout state.
- If flame is established and lost after 10 seconds, the control will recycle this series of 3 tries four more times before locking out.
Light: The diagnostic light will indicate this condition with one short on flash followed by a longer off.
Reset: The control can be reset and brought out of lockout mode by turning the thermostat off and then back on.
Qty |
Possible Causes (From Most to Least Likely): |
2 |
Bad Ignitor/Glow Plug |
3 |
Dirty flame sensor |
|
No Gas |
|
Clogged Burners |
|
Bad Gas Valve |
1 |
Bad Ignition Control |
CHECKOUT:
1. Check Glow Plug
- Look for any visual cracks.
- Use a meter to test resistance of glow plug.
- No Resistance = Bad Glow Plug
- Check for 120V power to the Glow Plug during an ignition sequence.
- No Power = Bad Ignition Control
- Power + Not Glowing = Bad Glow Plug
2. Check Ignition
- Visually inspect the burners during ignition.
- Burners should light with little or no delay from the glow plug to the flame sensor.
- Make sure the flame sensor comes in good contact with the flame.
- The glow plug should de-energize once flame is established.
- Glow Plug Does Not De-Energize = Bad Control Board
3. Check Gas Valve
- Turn off power to the furnace and close the gas safety shut-off valve.
- Hook-up a gas pressure gauge to the inlet test port of the gas valve.
- Open the gas safety shut-off and check gas pressure.
- Should be minimum of 5" w.c. for Nat. gas and 11" w.c. for propane.
- No Pressure = Gas Shut-Off ⇒ Check the Meter
- Low Pressure = Bad Meter or Regulator
- Re-apply power to the furnace and activate a call for heat.
- Check for 24VAC between the two gas valve feed wires at the time of ignition.
- No Power = Bad Ignition Control or Bad Wires
- Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
- Pressure Drops Below Minimum = Bad Meter or Regulator
- Turn off power to the furnace and close the gas safety shut-off.
- Move the gas pressure gauge to the manifold (leaving) test port on the gas valve.
- Be sure to put the plug back in the inlet test port before proceeding!
- Open the gas safety shut-off valve and re-apply furnace power.
- Activate a call for heat and monitor the manifold gas pressure during an ignition attempt. (3-3.5" w.c. for Nat. Gas, 9-11" w.c. for LP)
- No Pressure = Bad Gas Valve
- Good Pressure + No Ignition = Clogged Burners ⇒ Remove burners and clean spreaders
4. Check Flame Sensor
- DO NOT clean the flame sensor before checking!
- On the multi-meter:
- Switch the test leads to "COM" and "mA".
- Set the meter on DC 200ù.
- Disconnect the wire from the flame sensor.
- Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
- Check the reading when the burners ignite.
- Minimum acceptable reading = 1 MicroAmp
- Low Reading = Dirty Flame Sensor ⇒ Clean Flame Sensor & Re-check
- Normal Reading (2 to 6 mA) but still shuts-off = Bad Ignition Control
- MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!