Knowledgebase

GUC/GUX - Flashing Code 1

Article ID: 178
Last updated: 16 Nov, 2018

Amana Gas Furnace; GUC/GUX

Re: Flashing Code 1

  • If a flame was not sensed during the first 7 seconds after the gas valve was energized, the control turns off the gas.
  • The control will make 3 tries before it determines that it cannot establish measureable combustion and enters a lockout state.
  • If flame is established and lost after 10 seconds, the control will recycle this series of 3 tries four more times before locking out.

Light: The diagnostic light will indicate this condition with one short on flash followed by a longer off.

Reset: The control can be reset and brought out of lockout mode by turning the thermostat off and then back on.


Qty Possible Causes (From Most to Least Likely):
2 Bad Ignitor/Glow Plug
3 Dirty flame sensor
No Gas
Clogged Burners
Bad Gas Valve
1 Bad Ignition Control


CHECKOUT:

1. Check Glow Plug

  • Look for any visual cracks.
  • Use a meter to test resistance of glow plug.
    • No Resistance = Bad Glow Plug
  • Check for 120V power to the Glow Plug during an ignition sequence.
    • No Power = Bad Ignition Control
    • Power + Not Glowing = Bad Glow Plug

2. Check Ignition

  • Visually inspect the burners during ignition.
    • Burners should light with little or no delay from the glow plug to the flame sensor.
    • Make sure the flame sensor comes in good contact with the flame.
    • The glow plug should de-energize once flame is established.
      • Glow Plug Does Not De-Energize = Bad Control Board

3. Check Gas Valve

  • Turn off power to the furnace and close the gas safety shut-off valve.
  • Hook-up a gas pressure gauge to the inlet test port of the gas valve.
  • Open the gas safety shut-off and check gas pressure.
    • Should be minimum of 5" w.c. for Nat. gas and 11" w.c. for propane.
      • No Pressure = Gas Shut-Off ⇒ Check the Meter
      • Low Pressure = Bad Meter or Regulator
  • Re-apply power to the furnace and activate a call for heat.
  • Check for 24VAC between the two gas valve feed wires at the time of ignition.
    • No Power = Bad Ignition Control or Bad Wires
  • Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
    • Pressure Drops Below Minimum = Bad Meter or Regulator
  • Turn off power to the furnace and close the gas safety shut-off.
  • Move the gas pressure gauge to the manifold (leaving) test port on the gas valve.
    • Be sure to put the plug back in the inlet test port before proceeding!
  • Open the gas safety shut-off valve and re-apply furnace power.
  • Activate a call for heat and monitor the manifold gas pressure during an ignition attempt. (3-3.5" w.c. for Nat. Gas, 9-11" w.c. for LP)
    • No Pressure = Bad Gas Valve
    • Good Pressure + No Ignition = Clogged Burners Remove burners and clean spreaders

4. Check Flame Sensor

  • DO NOT clean the flame sensor before checking!
  • On the multi-meter:
    • Switch the test leads to "COM" and "mA".
    • Set the meter on DC 200ù.
    • Disconnect the wire from the flame sensor.
    • Place one meter lead on the flame sensor terminal and the other on the flame sensor wire.
    • Check the reading when the burners ignite.
      • Minimum acceptable reading = 1 MicroAmp
        • Low Reading = Dirty Flame SensorClean Flame Sensor & Re-check
        • Normal Reading (2 to 6 mA) but still shuts-off = Bad Ignition Control
    • MOVE SENSOR LEADS BACK TO "COM" and "V" BEFORE PROCEEDING!

This article was:   Helpful | Not helpful
Report an issue
Article ID: 178
Last updated: 16 Nov, 2018
Revision: 21
Access: Public
Views: 85
Comments: 0