Knowledgebase

GR6GD Fault Codes/Status Codes

Article ID: 747
Last updated: 9 Apr, 2024

Nordyne / Partners Choice - GR6GD

Re: Lockout Codes / Status Codes

Red Light Status Description
1 Limit Circuit Open
2 Pressure switch stuck open
3 Pressure switch stuck closed
4 Ignition failure
5 Reversed Polarity
Continuous Flash Flames sensed with gas valve off
Off Power off
Yellow Light Status Description
Continuous Flash Low flame signal
On Flame present
This article was:   Helpful | Not helpful
Report an issue
Article ID: 747
Last updated: 9 Apr, 2024
Revision: 3
Access: Public
Views: 156
Comments: 0