Ameristar Gas Furnace: A951X
Re: Flashing E3_2
E3_2 = Furnace Pressure Switch failed to close on a call for heat.
- There are 2 Pressure Switches - one connected to the inducer and one connected to the drain line.
- The Pressure Switch connected to the inducer is the only one that will cause the E3_2 code.
Qty |
Possible Causes: |
|
Bad Inducer Motor |
|
Water in inducer |
|
Clogged or Restricted Vent |
|
Bad Vent Pressure Switch |
|
Pressure Hose Problem |
|
Item Stuck in Inducer Motor |
1 |
Loose Inducer Assembly |
CHECKOUT:
1. Check Control Board
- Start the furnace with a call for heat.
- Ensure that power is present on "W" by checking for 24VAC between "W" and "C".
- No Power = No Call for Heat
- Power = The Inducer motor should start within 15 seconds.
- Inducer Motor Starts → Step 2. Check Inducer
- Inducer Motor Does Not Start + E3_2 ⇒ Check for 115V power to inducer.
2. Check Inducer
- Observe and listen to the inducer motor.
- Inducer motor runs normally → Step 3. Check Pressure Switch
- Inducer motor hums but does not start = Bad Inducer Motor/Capacitor or Item in Inducer ⇒ Remove inducer & check
- Sound of Water "Slurshing" = Water in Inducer ⇒ Remove Inducer, pour out water, re-install inducer ⇒ Check Condensate Drainage
- Listen for the sound of air sucking around the seal where the inducer assembly attaches to the heat exchanger.
- May need to tighten mounting screws to improve seal.
- Listen for sounds of water in the vent piping (near the furnace and at the vent termination).
- If water is gurgling in the vent, look for sags or low spots in the vent piping that will hold water.
- The vent piping must have a constant slope back toward the furnace.
3. Check Pressure Switch
- Make sure there are no sags in the pressure switch hoses that could hold water.
- Start the furnace with a call for heat.
- Check Vent Switch (Connected to the Inducer)
- Switch Contacts
- At the Pressure Switch
- With the wires attached to the switch, check for 24VAC between each terminal of the Pressure Switch and Common (YL/3 and OR/11)
- 24VAC On Both Sides = Switch Closed
- 24VAC On One Side Only = Open Switch ⇒ Use a pressure meter to check the Switch Pressure (below).
- At the Control Board
- At the 10-Pin Plug of the Furnace Control Board, check for 24VAC between Terminal#3 OR/11 and Common.
- Then check for 24VAC between Terminal#9 YL/3 and Common.
- 24VAC On Both Sides = Switch Closed
- 24VAC On One Side Only = Open Switch ⇒ Use a pressure meter to check the Switch Pressure (below).
- Switch Pressure
- Remove the Pressure Switch hose from the Inducer Motor.
- Inspect the pressure switch hose for a:
- Loose hose
- Dry-rotted, cracked hose
- Clogged hose
- Inspect the port on the inducer motor for any clog or restriction.
- Connect a pressure meter to the Inducer Motor pressure port.
- Compare actual pressure to the pressure rating on the switch.
- Pressure Near or Below Rating = Clogged or Restricted Vent
- Pressure Well Above the Rating + Open Switch = Bad Switch or Water in Switch