Knowledgebase

GULA - Flashing Code 3

Article ID: 712
Last updated: 13 Feb, 2023

Amana Gas Furnace: GULA

Re: Flashing Code 3

If, after the vent blower is energized, the pressure switch does not close, the control will keep the blower on and wait for the switch to close. The diagnostic code for this problem is 3 short flashes followed by a pause.

► The diagnostic code will go away once the pressure switch closes.


Qty Possible Causes:
3 Bad Inducer Motor
Bad Pressure Switch
Item Stuck in Inducer Motor
1 Bad Inducer Blower Wheel
1 Bad Ignition Control


CHECKOUT:

1. Check Control Board

  • Start the furnace with a call for heat.

2. Check Inducer Motor

  • Observe and listen to inducer motor operation.
    • Inducer Motor Starts and Runs Normally → Step 3. Check Pressure Switch
    • Inducer Starts buts Is Unusually Loud = Bad Inducer Blower Wheel or Item in Inducer ⇒ Remove inducer & check.
    • Inducer Motor Hums but Does Not Start = Bad Inducer Motor/Capacitor or Item in Inducer ⇒ Remove inducer & check.

3. Check Pressure Switch

  • Switch Contacts
  • Check for 24VAC between each side of the pressure switch and GND.
    • Power on One Side Only = Switch Not Closed ⇒ Check Switch Pressure (below)
    • Power on Both Sides + Code 3 ⇒ Check power at 12-pin plug
      • Check for 24VAC at Terminal #12 of the 12-pin plug (GY-12).
      • Check for 24VAC at Terminal #7 of the 12-pin plug (OR-22).
        • Power on One Terminal Only = Pressure Switch Circuit Open
        • Power on Both Terminals + Code 3Bad Control Board
  • Switch Pressure
  • Use a pressure meter to check the pressure at the switch.
  • Compare actual pressure to pressure rating on the switch.
    • Pressure Near or Below Rating = Blocked or Restricted Vent or Bad Inducer Blower Wheel
    • Pressure Well Above Rating + Switch Not Closed = Bad Switch 
This article was:   Helpful | Not helpful
Report an issue
Article ID: 712
Last updated: 13 Feb, 2023
Revision: 5
Access: Public
Views: 32
Comments: 0