Lennox EL195 Flashing Code 9

Article ID: 644
Last updated: 3 Nov, 2020

Lennox Gas Furnace: EL195UH

Re: Flashing Code 9

Code 9 = Furnace Pressure Switch Open with Inducer On


Qty Possible Causes:
Bad Inducer Motor
Water in the vent (improper slope)
Clogged or Restricted Vent
Bad Pressure Switch
Clogged / Frozen Drain
Item Stuck in Inducer Motor
Bad Control Board


CHECKOUT:

1. Check Control Board

  • Start the furnace with a call for heat.
  • Ensure that power is present on "W" by checking for 24VAC between "W" and "C".
    • No Power = No Call for Heat
    • Power = The Inducer motor should start within 15 seconds.

2. Check Inducer

  • Observe and listen to the inducer motor.
    • Inducer motor runs normally → Step 3. Check Pressure Switch
    • Inducer motor hums but does not start = Bad Inducer Motor/Capacitor or Item in Inducer ⇒ Remove inducer & check
    • Sound of Water "Slurshing" = Water in Inducer ⇒ Remove Inducer, pour out water, re-install inducer → Step 4.  Check Condensate Drainage
  • Listen for sounds of water in the vent piping (near the furnace and at the vent termination).
    • If water is gurgling in the vent, look for sags or low spots in the vent piping that will hold water.
      • The vent piping must have a constant slope back toward the furnace.

3. Check Pressure Switch

  • Start the furnace with a call for heat.
  • ​​​​Check Vent Switch 
    • Switch Contacts
    • With the wires attached to the switch, check for 24VAC between each terminal of the switch and Common.
      • 24VAC On Both Sides = Switch Closed 
      • 24VAC On One Side Only = Open Switch ⇒ Use a pressure meter to check the pressure at the switch.
    • Switch Pressure
    • Remove the Pressure Switch hose from the Inducer Motor.
    • Connect a pressure meter to the Inducer Motor pressure port.
    • Compare actual pressure to the pressure rating on the switch.
      • Pressure Near or Below Rating = Clogged or Restricted Vent
      • Pressure Well Above the Rating + Open Switch = Bad Switch or Water in Switch
      • ​​​​Water in Switch is usually caused by a mis-run pressure switch hose.

4. Check Condensate Drainage

  • Check the drain hose from the collector box.
    • Make sure all drain hoses are clear and have a downward slope.
  • In extreme cold conditions be cautious of Frozen Drains.