Lennox Gas Furnace: G20Q
Re: Burners Won't Ignite
These furnaces use a Honeywell spark ignition control and universal electronic ignition (3-wire) gas valve.
- When the ignition control receives 24VAC on "TH" it should start sparking through the ignition cable and send power out "PV" to open the Pilot Valve of the gas valve.
- Once pilot flame is sensed, the ignition control should send power out "MV" to open the Main Valve of the gas valve and ignite the burners.
► The ignition control only senses pilot flame, so any ignition faults will be related to the pilot flame only.
Qty |
Possible Causes: |
|
Low Pilot Flame |
|
Dirty Flame Sensor |
1 |
Bad Ignition Control |
|
Bad Gas Valve |
|
Damper End Switch |
|
Roll-Out Switch Open |
|
Limit Switch |
|
Low Gas Pressure |
CHECKOUT
1. Check Power
- Check for 24VAC between "R" and "T" on the low voltage wiring.
2. Check Ignition Sequence
- Set the thermostat to call for Heat
- Check for 24VAC between "W" and "T" on the low voltage wiring.
- No Power = No Heat Call ⇒ Check Thermostat
- Check for 24VAC on "W" output at the main control board.
- No Power = Open Limit or Bad Control Board ⇒ Check Limit Switch
- Check for 24VAC at the Ignition Control between "TH" and "TR".
3. Check Safeties
- With the thermostat calling for heat, check each of the following safeties:
- Damper End Switch
- Check for 24VAC between each side of the damper end switch and "T".
- Power on Both Sides = Damper Switch Closed ⇒ Check Roll-Out Limit
- Power on One Side Only = Damper Switch Open ⇒ Check damper/motor
- Roll-Out Limit
- Check for 24VAC between each side of the roll-out limit switch and "T".
- Power on Both Sides = Limit Switch Closed ⇒ Check Primary Limit
- Power on One Side Only = Limit Switch Open ⇒ Check Heat Exchanger
- Vent Safety Limit
- Check for 24VAC between each side of the vent limit switch and "T".
- Power on Both Sides = Limit Switch Closed
- Power on One Side Only = Limit Switch Open ⇒ Check for restricted vent.
4. Check Ignition Control
- Once 24VAC is present on "TH" of the ignition control, the pilot should try to light.
5. Check Gas Valve/Pilot
- At the Ignition Control, check for 24VAC between "PV" and "MV/PV".
- Power on "TH" + No Power on "PV" = Bad Ignition Control or Control Locked-Out ⇒ Cycle power then re-check.
- Power Present ⇒ Continue
- Turn the gas valve to the "Off" position.
- Remove the pilot line from the gas valve and turn the valve back "On".
- Check for pilot gas leaving the gas valve.
- Power on "PV" + No Pilot Gas = No Gas Supply or Bad Gas Valve
- Pilot Gas Present ⇒ Re-attach pilot line, clean the pilot orifice and re-check.
6. Check Gas Valve/Main
- Make sure the pilot flame makes good contact with the flame sensor.
- Little or No Contact ⇒ Increase Pilot Pressure
- Good Contact + No Main Gas ⇒ Check for 24VAC between "M" and "P/M" at the gas valve.
- No Power = Bad Ignition Control
- Power + No Ignition = No or Low Gas Supply or Bad Gas Valve ⇒ Check Gas Pressure