Climatemaster - Flashing Code 9

Article ID: 487
Last updated: 8 Feb, 2023

CLIMATEMASTER GEOTHERMAL

Re: Code 9

Code 9 = FP1 & FP2 Switched

  • During test mode, the control monitors to see if the FP1 and FP2 thermistors are in the appropriate places.
  • If the control is in test mode, the control will lockout, with code 9, after 30 seconds if:
    • a) The compressor is on in the cooling mode and the FP1 sensor is colder than the FP2 sensor
    • b) The compressor is on in the heating mode and the FP2 sensor is colder than the FP1 sensor

WHAT TO LOOK FOR:

  • Bad FP1 or FP2 sensor (see sensor resistance chart)
  • Switched sensor locations.
    • Violet (FP2) should be on the left-hand side of the expansion valve
    • Gray (FP1) should be on the right-hand side.