AHP Air Handler - Won't Stop Heating/Runs Continuous

Article ID: 456
Last updated: 6 Feb, 2023

York Air Handler: MP, AHP

Re: Won't Stop Heating/Runs Continuous

The auxiliary heaters are controlled by a computer board and DC voltage relays.


Qty Possible Causes:
1 Bad Thermostat
Shorted Low Voltage
Bad Heater Relays
Bad Heater Control Board
Shorted Heaters
Bad Defrost Board
1 Stuck Compressor Contactor

Checkout:

1. Check Outdoor Unit & Air Handler

  • Outdoor
  • Check to see if the outdoor unit is operating.
  • Air Handler
  • Do not turn off power to the air handler or you will lose diagnostic codes.
  • Remove the blower access panel.
    • Be cautious not let the panel insulation suck in.
  • Check the control board for any active faults.
    • Fault Code + Heating ⇒ Report to Supervisor

2. Check Low Voltage


3. Check Thermostat

  • Check to see if the thermostat is call for heat.
    • Calling for Heat ⇒ Adjust the setpoint and see if heat goes off.
    • No Call for Heat + Heat Running ⇒ Continue
  • Remove the thermostat from the sub-base.
  • Re-check 24VAC power on "W1" and "W2" at the air handler.
    • Power Goes Away = Bad Thermostat
    • Power Still Present ⇒ Remove the White wire from the sub-base & Re-check voltage.
      • Power Goes Away = Bad Sub-base
      • Power Still Present ⇒ Remove "W1" and "W2" from the air handler.

4. Check Heaters

  • Identify any operating using an Amp Probe to check amperage on each heater (approx. 18 amps per heater).
  • Check voltage across any operating heater.

5. Check Board & Relays

  • Trace any operating heater back to its controlling relay.
  • Check for 22VDC on the coil of the relay.
    • ​​​​​​​No 24VAC + No 22VDC + Heater On = Bad Relay
    • No 24VAC + 22VDC = Bad Heater Control Board