Knowledgebase

58ZAV - Flashing Code 34

Article ID: 423
Last updated: 13 Mar, 2018

Carrier Gas Furnace: 58ZAV

Re: Flashing Code 34

Code 34 = Failure to Sense Flame 

Flash Sequence = 3 Short Flashes + 4 Long Flashes (- - - , — — — —)


Qty Possible Causes:
Dirty Flame Sensor
Bad Glow Plug
Clogged Burners
No or Low Gas Pressure
Bad Gas Valve
Bad Control Board


CHECKOUT:

1. Check Ignition Sequence

  • Initiate a call for heat from the thermostat and monitor the ignition sequence.
  • If there is 24V on "W" at power-up, the furnace will run the blower for 90 seconds and flash a Code 12.
    • 1. The inducer motor should start with no difficulty.
    • 2. The glow plug should energize within 30 seconds of the pressure switch closing.

2. Check Glow Plug

  • Use a meter to test resistance of the glow plug.
    • No Resistance = Bad Glow Plug
  • Re-start an ignition sequence.
  • Check for 120VAC power on the 2-wire plug feeding the glow plug during an ignition sequence.
    • No Power = Bad Ignition Control
    • Power Present + No Glow = Bad Glow Plug

3. Check Ignition

  • Visually inspect the burners during ignition.
    • The burners should light smoothly with little or no delay from the glow plug to the flame sensor.
    • Make sure the flame sensor comes in good contact with the flame.

4. Check Gas Pressure / Valve

  • Check Inlet Gas Pressure
    • Minimum Pressure = 5" w.c. for Nat. gas, and 10" w.c. for LP.
      • Low Pressure = Gas Supply Issue
    • Re-apply power to the furnace and activate a call for heat.
    • Make sure the inlet gas pressure stays above minimum when the gas valve energizes.
      • Pressure Drops Below Minimum = Gas Supply Issue
  • Check Manifold Gas Pressure
    • Normal Pressure = 3 to 3.5" w.c. for Nat. Gas, 9 to 11" w.c. for LP.
    • Activate a call for heat and monitor the manifold gas pressure during an ignition attempt.
      • No Gas Pressure = Bad Gas Valve
      • Low Gas Pressure ⇒ Attempt to Increase Manifold Gas Pressure
        • Won't Increase = Bad Gas Valve
      • Normal Gas Pressure + No or Delayed Ignition = Clogged Burners ⇒ Remove burners and clean spreaders

5. Check Flame Sensor

  • Check the flame sensor reading when the burners ignite.
    • Normal Reading = 2 to 6 mA
    • Minimum acceptable reading = 1 MicroAmp
      • Normal Reading + Burners Shut-Off after 4-6 seconds = Bad Control Board
      • Low Reading = Dirty Flame Sensor ⇒ Clean the Flame Sensor & Re-check
  • CAUTION! Move meter leads back to "COM" and "V" before proceeding!
This article was:   Helpful | Not helpful
Report an issue
Article ID: 423
Last updated: 13 Mar, 2018
Revision: 7
Access: Public
Views: 40
Comments: 0