AHX/MX Air Handler - Flashing Code 3 - Fan Running Continuous

Article ID: 404
Last updated: 27 Feb, 2024

York Air Handler: AHX/MX

Re: Flashing Code 3 - Fan Running Continuous

The control board in the air handler monitors the limit switch in the aux heaters.

If the limit switch opens multiple times during a single call for electric heat the control will flash a Code 3 and energize the blower until power is removed from the control.

The control will continue to cycle the heat outputs on and off as the limit re-closes and opens.

The constant fan operation will signal the homeowner that a problem has occurred and a service call is required.

► The diagnostic light at the thermostat will NOT flash or provide any indication.


To reset: Line or Low Voltage Power to the air handler control board must be cycled.


Qty Possible Causes:
6 Clogged/Restrictive Air Filter
3 Heat Fan Speed too Low
High Duct Static
Failing X-13 Motor
1 Insulation Against Blower
1 Bad Control Board
Bad Limit(s)

Checkout:

1. Check Cabinet Insulation

  • Open the blower compartment and look for loose insulation that could block one or both sides of the blower.
    • The most effective repair is to screw one or more metal straps the full length of the loose insulation.

2. Check for Water on Control Board

  • Especially in counter-flow applications, the control board is extremely susceptible to water damage from condensate overflow.
    • If there is water in the base of the air handler, or if the control board has obvious signs of water damage ⇒ suspect a Bad Control Board

3. Check Limits & Board

  • Turn off power to the air handler.
    • It is best to turn off power at the breaker box as this test may bring you into contact with the inlet power wiring.
  • Disconnect the white molex plug from the air handler control board.
  • On the plug (not the board) check resistance between the Red and Brown wires.
    • No Resistance Red to Brown Open Limit
    • Resistance Red to Brown = Limit circuit closed  Re-attach molex plug and re-power air handler.
      • Still Code 3 or 4 = Bad Control Board

4. Check Blower Speeds/Operation

  • Activate a call for Fan by one of the following methods:
    • At the thermostat, turn the "Fan" switch to "On".
    • At the air handler control board, place a jumper wire between "R" and "G".
  • X-13 Motor (AHX/MX)
    • Check high voltage plug for 230VAC
    • Check for 24VAC between "C" and "Red" at motor.
      • 230VAC + 24VAC on Red + No Blower = Bad Blower Motor
      • 230VAC + No 24VAC = Bad Control Board

5. Check Air Filter

  • With the filter in, run the unit in "Em Heat" and check the temperature rise.
  • Remove the air filter and recheck the temperature rise.
    • Little or No Change = Filter (may need replaced but) Not the Cause
    • Big Change = Clogged or Restrictive Air Filter
      • Be cautious of the expensive 3M Filters from Lowes (Very Restrictive!)