Package Unit: DNQ Re: Code 2 There are 2 control boards on this unit, a CFM Selector Board (CFMCB) which controls the variable speed blower motor and an Ignition Control Board (ICB). The ICB controls the inducer fan, spark ignition and gas valve. ► All heating diagnostics will be displayed on the ICB. CODE 2 = Pressure switch "Open" with the inducer motor energized.
CHECKOUT: 1. Check Heating Sequence