DNQ - V/S Motor Not Running - Cooling

Article ID: 548
Last updated: 30 Jan, 2023

York Package Unit: DNQ

Re: Variable Speed Blower Not Running - Cooling

The unit is calling for either Fan or Cooling, but the indoor blower is not operating.


Qty Possible Causes:
1 Bad Blower Motor
Bad Control Board

CHECKOUT:

1. Check Operation


2. Check Line Voltage Power

  • At the outdoor unit, remove the filter/control access panel.
  • Look for any signs of burnt wires or controls.
  • Check resistance across each fuse.
    • No Resistance = Blown Fuse
  • Check for 230V power across each power supply.
    • No Power = Check Breaker Panel, Bad Breaker

3. Check Low Voltage Power

  • Check for 24VAC between "R" and "C" on the low voltage wiring.
    • No Power = Blown Low Voltage Fuse or Bad Transformer
  • Check for 24VAC between "G" and "C" on the low voltage wiring.
  • Check for 24VAC between "Y" and "C" on the low voltage wiring.

4. Check Blower Motor

  • Check Blower Motor
    • Check for 230V across blower motor "Prp" at Pin#4 and "Blk" at Pin#5 on the ECM motor.
      • No Power = Blown Fuse
    • Check for 24VAC between "G/Pr" at Pin#15 and "C1/Br" at Pin#1.
      • Power + No Fan Operation = Bad ECM Motor