DNQ - Flashing Code 2

Package Unit: DNQ

Re: Code 2

There are 2 control boards on this unit, a CFM Selector Board (CFMCB) which controls the variable speed blower motor and an Ignition Control Board (ICB). The ICB controls the inducer fan, spark ignition and gas valve.

► All heating diagnostics will be displayed on the ICB.

CODE 2 = Pressure switch "Open" with the inducer motor energized.


Qty Possible Causes:
Bad Inducer Motor
Bad Pressure Switch
1 Clogged Pressure Port
Item Stuck in Inducer Wheel
Bad Ignition Control Board

CHECKOUT:

1. Check Heating Sequence


2. Check Control Board


3. Check Inducer


4. Check Pressure Switch



Article ID: 380
Last updated: 30 Jan, 2023
Revision: 10
Equipment -> Package Units -> York -> DNQ -> DNQ - Flashing Code 2