Knowledgebase

GPG13 - Flashing Code 3

Article ID: 262
Last updated: 18 Jan, 2022

Goodman Package Unit: GPG13

Re: Flashing Code 3

Code 3 = Pressure switch failed to open (stuck closed)

The furnace pressure switch should only close when the inducer fan output is energized. If control board is not energizing the inducer fan output and the switch is closed, the board will flash a code 3.

► A Code 3 may keep the inducer motor from starting on a call for heat.


Qty Possible Causes (From Most to Least Likely):
1 Bad Pressure Switch
Inducer Fan Stuck On (Bad Control Board)
ADPS Switch Set Too Low


CHECKOUT:

1. Check Controller

  • Check for 24VAC power from "W" to "C".
    • Inducer fan should not be operating with no power on "W".
      • Inducer may continue to run for "post-purge" after a call for heat for up to 30 seconds.
      • Inducer may also run if a limit is tripped.

2. Check Pressure Switch Contacts

  • DO NOT PULL WIRES OFF OF SWITCH - MAY RESET CONTACTS!
  • Check for 24VAC from both sides of the switch to "C".
    • Power on both sides = Switch Closed
    • Power on only one side = Switch Open

3. ADPS Switch Setting

  • The ADPS switch will sometimes fail to re-open when set for the lowest setting.
This article was:   Helpful | Not helpful
Report an issue
Article ID: 262
Last updated: 18 Jan, 2022
Revision: 4
Access: Public
Views: 66
Comments: 0