GPG13 - Flashing Code 3

Goodman Package Unit: GPG13

Re: Flashing Code 3

Code 3 = Pressure switch failed to open (stuck closed)

The furnace pressure switch should only close when the inducer fan output is energized. If control board is not energizing the inducer fan output and the switch is closed, the board will flash a code 3.

► A Code 3 may keep the inducer motor from starting on a call for heat.


Qty Possible Causes (From Most to Least Likely):
1 Bad Pressure Switch
Inducer Fan Stuck On (Bad Control Board)
ADPS Switch Set Too Low


CHECKOUT:

1. Check Controller


2. Check Pressure Switch Contacts


3. ADPS Switch Setting



Article ID: 262
Last updated: 18 Jan, 2022
Revision: 4
Equipment -> Package Units -> Goodman -> GPG13 -> GPG13 - Flashing Code 3