Knowledgebase

YCY - Ignition Control Faults

Article ID: 248
Last updated: 13 Mar, 2017

Trane Package Unit: YCY

Re: Ignition Lockout Codes

Trane YCY package units are 2-Stage Gas Heat, 1 Stage Cooling units.

  • These units utilize an Ignition Control Board (ICB) with a built-in spark generator for electronic ignition control.
  • The ICB has a diagnostic light to indicate heat status.

Red Light Status Description
Slow Flash Normal, No call for Heat
Fast Flash Normal, Call for Heat
Continuous On Replace Control
Off Check Control Power
2 Lockout - No Flame Sensed
3 Pressure Switch Problem
4 High Limit (TCO) Open
5 Flame Sensed with Gas Valve Off
6 Flames Rollout Switch (FL) Open