Trane YCY package units are 2-Stage Gas Heat, 1 Stage Cooling units.


Red Light Status Description
Slow Flash Normal, No call for Heat
Fast Flash Normal, Call for Heat
Continuous On Replace Control
Off Check Control Power
2 Lockout - No Flame Sensed
3 Pressure Switch Problem
4 High Limit (TCO) Open
5 Flame Sensed with Gas Valve Off
6 Flames Rollout Switch (FL) Open